beautypg.com

Detcon IR-622 User Manual

Page 8

background image

3.4.3.1 Program Status

The program status scrolls through a menu that displays:

* The gas type, range of detection and software version number. The menu item appears as:

“LEL 0-100 V6.0”

* The alarm set point level of alarm 1. The menu item appears as:

“ALM1 SET @ ##%”

* The alarm f iring direction of alarm 1. The menu item appears as:

“ALM1 ASCENDING” or descending.

* The alarm relay latch mode of alarm 1. The menu item appears as:

“ALM1 NONLATCHING” or latching.

* The alarm relay energize state of alarm 1. The menu item appears as:

“ALM1 DE-ENERGIZED” or energized.

* The alarm set point level of alarm 2. The menu item appears as:

“ALM2 SET @ ##%”

* The alarm f iring direction of alarm 2. The menu item appears as:

“ALM2 ASCENDING” or descending.

* The alarm relay latch mode of alarm 2. The menu item appears as:

“ALM2 LATCHING” or nonlatching.

* The alarm relay energize state of alarm 2. The menu item appears as:

“ALM2 DE-ENERGIZED” or energized.

* The alarm relay latch mode of the fault alarm. The menu item appears as:

“FLT NONLATCHING” or latching.

* The alarm relay energize state of the fault alarm. The menu item appears as:

“FLT ENERGIZED” or deenergized.

* The calibration gas level setting. The menu item appears as:

“CalLevel @ xx%”

* Identif ication of the RS-485 ID number setting. The menu item appears as:

“485 ID SET @ ##”

* Sensor temperature in °C appears as:

“TEMPERATURE xx °C”

* The estimated remaining sensor life. The menu item appears as:

“OPTICS AT 100%”

3.4.3.2 Alarm 1 Level Adjustment

The alarm 1 level is adjustable over the range 10 to 90%. For combustible gas sensors, the level is factory set at

20%. The menu item appears as:

“SET ALM1 @ 20%”

3.4.3.3 Alarm 2 Level Adjustment

The alarm 2 level is also adjustable over the range 10 to 90%. For combustible gas sensors, the level is factory set at

60%. The menu item appears as:

“SET ALM2 @ 60%”

3.4.3.4 Calibration Level Adjustment

The Calibration level is adjustable from 10% to 90% LEL. The menu item appears as:

“CalLevel @ ##%”

3.5 I

NSTALLATION

Optimum performance of ambient air/gas sensor devices is directly relative to proper location and installation practice.

3.5.1 Field Wiring Table (4-20 mA output)

Detcon Model IR-622 combustible gas sensor assemblies require three conductor connection between power sup-

plies and host electronic controllers. Wiring designators are + (DC), (DC) , and mA (sensor signal). Maximum

single conductor resistance between sensor and controller is 10 ohms. Maximum wire size for termination in the

sensor assembly terminal board is 14 gauge.

AWG

Meters

Feet

20

240

800

18

360

1200

16

600

2000

14

900

3000

Note 1: This wiring table is based on stranded tinned copper wire and is designed to serve as a reference only.

Note 2:

Shielded cable may be required in installations where cable trays or conduit runs include high voltage

lines or other sources of induced interference.

Note 3:

The supply of power must be from an isolating source with over-current protection as follows:

AWG

Over-current Protection

AWG

Over-current Protection

22

3A

16

10A

20

5A

14

20A

18

7A

12

25A

The RS-485 (if applicable) requires 24 gauge, two conductor, shielded, twisted pair cable between sensor and host

PC. Use Belden part number 9841. Two sets of terminals are located on the connector board to facilitate serial loop

wiring from sensor to sensor. Wiring designators are A & B (IN) and A & B (OUT).

Detcon Model IR-622 Combustible Hydrocarbon Sensor PG.8