tained, excessive loss in useable signal eventually gives way to noise and unstable readings. The optical sensor may, over long

periods of time (3-7 years), lose its IR lamp source filament, and in this case an optical sensor modular replacement is

required. The IR-622 has an extensive list of Fault Diagnostics to alert and pin-point operational problems. See section 3.10

3.2 A

PPLICATION

Model IR-622 MicroSafe™ sensors are designed to detect and monitor combustible hydrocarbon gas in ambient air in

the range of 0-100% LEL. Minimum sensitivity and scale resolution is 1%. Operating temperature range is -40° F. to

+175° F. While the sensor is capable of operating outside these temperatures, performance specifications are verified

within the limit.

3.2.1 Sensor Placement/Mounting

Sensor location should be reviewed by facility engineering and safety personnel. Area leak sources and perimeter mounting

are typically used to determine number and location of sensors. The sensors are generally located 2 - 4 feet above grade.

3.2.2 Response to Different Gases

The MicroSafe™ IR-622 responds to all combustible hydrocarbon gases, but at different signal strengths. In order to maintain

accurate readings, the detector must be calibrated to the specific target gas of interest.

The MicroSafe™ IR-622 is factory calibrated for the specific target gas chosen at the time of order. Unless otherwise speci-

fied by the customer, the detector will be factory calibrated for methane service. Once installed in the field, if a combustible

hydrocarbon gas other than the gas specified at the time of order is being measured, contact Detcon for the appropriate field-

replaceable electronics/software upgrade. The calibration gas used to span the IR-622 must be the same gas type as the target

gas being measured.

3.3 S

PECIFICATIONS

Method of Detection

NDIR Optical

Electrical Classification

Class I; Groups B, C, D; Div. 1.

Response Time

T50 < 15 seconds; T90 < 35 seconds

Detcon Model IR-622 Combustible Hydrocarbon Sensor PG.6

Functional

Block

Diagram

Functional

Block

Diagram

Analog 4-20 mA Out

Power In

Relays Out

Pre-Amp

Display

Temperature

Compensation

Alarm & Fault

Relays

RS-485 & 4-20mA

Micro-

processor

Transmitter

Power Supply

Optical

Sensor

I/O Circuit

Protection

Serial RS-485 Out

0

4

8

12

16

20

20

40

60

80

100

% LEL (lower explosive limit)

m

A

D

C

S

ig

n

a

l

O

u

tp

u

t

Output Response Curve