settings of the alarms (jumpers removed) are normally de-energized relays, non-latching relays, and alarm points

that activate during descending gas conditions.

If a jumper tab is installed in the latch position, that alarm relay will be in the latching mode. The latching

mode will latch the alarm after alarm conditions have cleared until the alarm reset function is activated. The non-

latching mode (jumper removed) will allow alarms to de-activate automatically once alarm conditions have cleared.

If a jumper tab is installed in the energize position, that alarm relay will be in the energized mode. The ener-

gized mode will energize or activate the alarm relay when there is no alarm condition and de-energize or de-acti-

vate the alarm relay when there is an alarm condition. The de-energized mode (jumper removed) will energize or

activate the alarm relay during an alarm condition and de-energize or de-activate the alarm relay when there is

no alarm condition.

If a jumper tab is installed in the ascending position, that alarm relay will be in the ascending mode. The

ascending mode will cause an alarm to f ire when the gas concentration detected is greater than or equal to the

alarm set point. The descending mode (jumper removed) will cause an alarm to f ire when the gas concentration

detected is lesser than or equal to the alarm set point. Except in special applications, combustible gas monitor-

ing will require alarms to f ire in “ASCENDING” gas conditions.

Any unused jumper tabs should be stored on the connector board on the terminal strip labeled “Unused

Jumpers” (see f igure 3).

f)

If applicable, set the RS-485 ID number via the two rotary dip switches located on the preamp board (see f igure

5). There are 256 different ID numbers available which are based on the hexidecimal numbering system. If RS-

485 communications are used, each sensor must have its own unique ID number. Use a jewelers screwdriver to

set the rotary dip switches according to the hexidecimal table listed below. If RS-485 communications are not

used, leave the dip switches in the default position which is zero/zero (0)-(0).

g)

Replace the plug-in control circuit and replace the junction box cover.

Detcon Model IR-622 Combustible Hydrocarbon Sensor PG.11

Preamp Board - Side View

RS-485 ID Set Dip Switches

Control Circuit - Side View

Preamp Board

0 12

3

4

5

6

78

9A

B

C

D

E

F

0 12

3

4

5

6

78

9A

B

C

D

E

F

SW2

SW1

Figure #5

FAULT

ALARM 1

Latch

Energize

Latch

Ascending

Energize

A

LA

R

M

2

La

tc

h

A

sc

en

di

ng

E

ne

rg

iz

e

CPU Board - Top View

Alarm Programming Jumpers

Control Circuit - Side View

CPU Board

Figure #4