Model TP-700

TP-700 Instruction Manual

Rev. 3.5

Page 36 of 38

11"H x 6.1"W x 3.75"D; 280mmH x 155mmW x 96mmD (with junction box)
Mounting holes (J-box) 5.5"; 140mm center to center

Weight:

2 lbs; 0.907kg (sensor only)
6 lbs; 2.72kg (w/aluminum j-box)
9 lbs; 4.08kg (w/stainless steel j-box)

Electrical Specifications

Input Voltage:

11-30 VDC

Power Consumption:

Normal operation = 68mA (<1.7 watt)
Maximum = 85mA (2 watts)

Inrush current:

1.0A @ 24V

RFI/EMI Protection:

Complies with EN61000

Analog Output:

Linear 4-20mA DC current (1000 ohms maximum loop load @ 24VDC)
0mA

All Fault Diagnostics

2mA

In-Calibration

4-20mA

0-100% full-scale

22mA

Over-range condition

Serial Output:

RS-485 Modbus™ RTU

Baud Rate:

9600 BPS (9600,N,8,1 Half Duplex)

Status Indicators:

4-digit LED Display with gas concentration
full-script menu prompts for AutoSpan,
Set-up Options, and Fault Reporting

Faults Monitored:

Heater, Loop, Input Voltage, Sensor, Processor, Memory, Calibration

Cable Requirements:

Power/Analog: 3-wire shielded cable

Maximum distance is 13,300 feet with 14 AWG

Serial Output: 2-wire twisted-pair shielded cable specified for RS-485 use

Maximum distance is 4,000 feet to last sensor

I/O Protection:

Over-Voltage, Miss-wiring, EMI/RFI Immunity