beautypg.com

Detcon TP-700 User Manual

Page 36

background image

Model TP-700

TP-700 Instruction Manual

Rev. 3.5

Page 32 of 38

Nuisance Alarms

 Check condulet for accumulated water and abnormal corrosion on terminal blocks.

 If nuisance alarms are happening at night, suspect condensation in condulet. Add or replace Detcon’s

Condensation Prevention Packet P/N 960-202200-000.

 Investigate the presence of other target gases that are causing cross-interference signals.

 Determine if cause is RFI induced.

Processor and/or Memory Faults

 Recycle power in attempt to clear problem

 Restore Factory Defaults - This will clear the processor’s memory and may correct problem.

Remember to re-enter all customer settings for range and cal gas level after Restore Factory Defaults.

 If problem persists, replace the Intelligent Sensor Module.

Unreadable Display

 If due to excessive sunlight, install a sunshade to reduce glare.

Nothing Displayed – Transmitter not Responding

 Verify condulet has no accumulated water or abnormal corrosion.

 Verify required DC power is applied to correct terminals.

 Swap with a known-good ITM to determine if ITM is faulty.

Faulty 4-20mA Output

If Sensor has a normal reading with no Faults displayed, and the 4-20 mA signal output is 0mA….

 Check that wiring is properly connected at terminal blocks and through to controller inputs.

 The 4-20mA output loop must be closed to avoid a Loop Fault. If the 4-20mA output is not being

used the green wire from the sensor must be connected to the (-) terminal on the Transient Protection
Module to ensure that it does not create a 4-20mA Fault. (section 2.6 Field Wiring)

 Perform a “Signal Output Check” sequence via Section 3.5.7 and verify 4-20mA output with Current

Meter.

 Swap with new ITM to determine if the ITM’s 4-20mA output circuit is faulty.

 If the 4-20mA current loop is still out of tolerance, contact Detcon at

[email protected]

, or contact

Detcon customer service.

No Communication - RS-485 Modbus™

If sensor has a normal reading with no Faults displayed and the Modbus™ is not communicating….

 Verify that the correct (and non-duplicated) serial address is entered (per Section 0).

 Check that the wiring is properly connected at terminal blocks, and the serial loop is wired correctly.

 Perform a “Signal Output Check” per Section 3.5.7 and troubleshoot wiring.

 Consider adding a Modbus™ repeater if the distance from the nearest distribution drop is excessive.

 Swap with new ITM to determine if the ITM’s serial output circuit is faulty.

 Refer to Detcon’s “Guide to Proper Modbus™ Communications” Application Note.