Detcon TP-700 User Manual
Page 36
Model TP-700
TP-700 Instruction Manual
Rev. 3.5
Page 32 of 38
Nuisance Alarms
Check condulet for accumulated water and abnormal corrosion on terminal blocks.
If nuisance alarms are happening at night, suspect condensation in condulet. Add or replace Detcon’s
Condensation Prevention Packet P/N 960-202200-000.
Investigate the presence of other target gases that are causing cross-interference signals.
Determine if cause is RFI induced.
Processor and/or Memory Faults
Recycle power in attempt to clear problem
Restore Factory Defaults - This will clear the processor’s memory and may correct problem.
Remember to re-enter all customer settings for range and cal gas level after Restore Factory Defaults.
If problem persists, replace the Intelligent Sensor Module.
Unreadable Display
If due to excessive sunlight, install a sunshade to reduce glare.
Nothing Displayed – Transmitter not Responding
Verify condulet has no accumulated water or abnormal corrosion.
Verify required DC power is applied to correct terminals.
Swap with a known-good ITM to determine if ITM is faulty.
Faulty 4-20mA Output
If Sensor has a normal reading with no Faults displayed, and the 4-20 mA signal output is 0mA….
Check that wiring is properly connected at terminal blocks and through to controller inputs.
The 4-20mA output loop must be closed to avoid a Loop Fault. If the 4-20mA output is not being
used the green wire from the sensor must be connected to the (-) terminal on the Transient Protection
Module to ensure that it does not create a 4-20mA Fault. (section 2.6 Field Wiring)
Perform a “Signal Output Check” sequence via Section 3.5.7 and verify 4-20mA output with Current
Meter.
Swap with new ITM to determine if the ITM’s 4-20mA output circuit is faulty.
If the 4-20mA current loop is still out of tolerance, contact Detcon at
, or contact
Detcon customer service.
No Communication - RS-485 Modbus™
If sensor has a normal reading with no Faults displayed and the Modbus™ is not communicating….
Verify that the correct (and non-duplicated) serial address is entered (per Section 0).
Check that the wiring is properly connected at terminal blocks, and the serial loop is wired correctly.
Perform a “Signal Output Check” per Section 3.5.7 and troubleshoot wiring.
Consider adding a Modbus™ repeater if the distance from the nearest distribution drop is excessive.
Swap with new ITM to determine if the ITM’s serial output circuit is faulty.
Refer to Detcon’s “Guide to Proper Modbus™ Communications” Application Note.