When possible mount in an area void of high wind, accumulating dust, rain or splashing from hose spray,
direct steam releases, and continuous vibration. If the sensor cannot be mounted away from these conditions
then make sure the Detcon Harsh Environment Splashguard accessory is used.

Do not mount in locations where temperatures will exceed the operating temperature limits of the sensor.
Where direct sunlight leads to exceeding the high temperature-operating limit, use a sunshade to help reduce
temperature.

2.3 Sensor Contaminants and Interference

Solid State H

2

S sensors may be adversely affected by exposure to certain airborne substances.

Loss of

sensitivity or corrosion may be gradual if such materials are present in sufficient concentrations.

The more common materials that potentially cause problems with the sensors are as follows:

 Silicone vapors such as those found in greases and lubricants

 Halide Compounds containing Chlorine, Chlorine Dioxide, Fluorine, HF, HCl, and Bromine

 Caustic and Acid liquids and concentrated vapors

 Heavy metals such as tetraethyl lead

The presence of such contaminants in an area does not preclude the use of this H

2

S sensor technology,

although it is likely that the sensor lifetime will be shorter as a result. Use of this sensor in these environments
may require more frequent calibration checks to ensure safe system performance.

Solid State H

2

S sensors require O

2

in the background gas and the reading is affected by changing O

2

levels.

Interference Data

There are some gases typically found in industrial environments that can cause a cross-interference response
on the sensor. See the Table below for some examples.

Table 1 Cross Interference Gases

GAS

PPM

GAS

PPM

Methane

25,000 = 0

Ammonia

500 = 1

Ethane

5,000 = 0

Diesel Fuel

1000 = 0

Hexane

5,000 = 0

Dimethyl Sulfide

4.4 = 0

Propane

5,000 = 0

Ethylene

200 = 0

Butane

5,000 = 0

Freon 12

1,000 = 0

Carbon Monoxide

800 = 0

Hydrogen

1,000 = 8

Carbon Dioxide

5,000 = 0

Methyl Mercaptan

10 = 5

Carbon Disulfide

14 = 0

Sulfur Dioxide

300 = 0

Methanol

500 = 5

Toluene

32 = 0

Isopropanol

500 = 3

Ethanol

500 = 5

NOTE: The Detcon MOS Sensor Cell can be damaged to the point of non-functioning if the
unit is left off power and in the presence normal air levels of moisture for periods exceeding 8
hours.

NOTE: Always protect the sensor cell with the Detcon Sealing Cap and a fresh desiccant