beautypg.com

Appendix b:hdt pin 3 timing diagrams, Pin 3 timing diagrams for the 4 possible modes, Hdt user’s manual page 20 – COSA Xentaur Xentaur HDT User Manual

Page 27

background image

HDT User’s Manual

page 20

Appendix B:HDT pin 3 timing diagrams

0

4

8

12

16

20

24

28

32

Time (sec)

power on

3V

0V

3V

0V

3V

0V

3V

0V

high impedance

high impedance

high impedance

high impedance

Pin 3 timing diagrams for the 4 possible modes

Pin 3 MODES

When in Digital

Echo mode

When in Fault

Reporting

mode

When in Alarm

Relay mode

When in Switch

Monitor mode

Low Voltage TTL (0-3V) in RS-232 inverted data format,

using HART protocol

Active = Spacing = RS-232 Positive Voltage : PIN3=high ~3V

Idle = Marking = RS-232 Negative Voltage : PIN3=low ~0V

High impedance when fault detected

Has highest precedence over other simultaneous modes

Low when no fault, has lowest precedence with other simultaneous modes

when neither alarm is triggered

(measurement is between Low & High Alarms)

when measurement is above High Alarm

when measurement is below Low Alarm

On the next HART message

HDT pulls pin 3

to 3.3V with a 10K resistor

Response Code byte 2, bit 6

PIN 3: Float =0, Ground =1

idle

idle

data

Note:

The Fault Reporting Mode can be utilized simultaneously with either the Digital Echo or Alarm Relay Modes.

However when a fault occurs the high impedance fault condition will override the other signaling.