beautypg.com

Van Air Systems D12-D36 User Manual

Page 9

background image

PAGE 9

SECTION 5

TROUBLESHOOTING

1. DECREASED PERFORMANCE - High desiccant usage.

High inlet air temperatures.

Check the aftercooler performance. Make sure that the

aftercooler was properly sized and installed. Check the aftercooler

operation manual for further details.

If an aftercooler was not installed, one may be required.

Check the compressor capacity or air usage vs. the dryer rating.

Was a different compressor installed?

High ambient temperatures.

Check the location of the dryer for changes in ambient tempera-

tures.

Was the dryer moved to a different location?

Was a piece of equipment or piping installed near the dryer that

caused an increase in ambient temperatures? Relocate the dryer

or equipment if possible. If relocation is not possible, correct the

ambient temperature.

Dryer overloaded.

Check the flow through the dryer. Check the flow at peak usage

periods. Have the flow requirements of the system increased?

Was the dryer properly sized for the actual operating conditions?

Check the capacity of the dryer for the system conditions. If the

system requirements exceed the dryer's capability, a larger dryer

must be installed.

Desiccant bed below required level.

Check the desiccant bed level. The level should be checked at

least once a month. The usage of desiccant will vary with the

operating conditions and the type of desicccant being used. The

dryer will require more desiccant during the warmer months of the

year.

Desiccant quantities and filling procedures are outlined in Section

4.4 of this manual.

2. LIQUID DOWNSTREAM OF THE DRYER.

Improper draining. The dryer may be flooded.

The dryer must be drained at least once for every 8 hours of

operation.

Check the drain valve(s) and piping for clogs. Repair or replace

faulty valves. If the piping is clogged, it must be cleared.

If the dryer is installed outdoors where ambient temperatures fall

below freezing, the drain line and valve(s) may freeze. If ambient

temperatures fall below freezing, the drain line can be wrapped

with heat tracing and/or insulation to prevent freezing.

If maintaining the required draining schedule is a problem, an

automatic ball type drain valve should be installed. Reference

Section 2.2-F in this manual for installation instructions.

IMPORTANT: Never install a float type or solenoid type drain valve

on this dryer.

Bypass valve open or faulty.

Check the dryer bypass valve. It might be faulty or open allowing

untreated air to enter the air system.

Low or no desiccant in the dryer.

Check the dryer deissiccant bed level. Reference Section 4.4 for

filling quantities and procedures.

3. DECREASED PERFORMANCE - low desiccant usage.

The desiccant bed may be contaminated.

The dryer will tolerate normal amounts of compressor lubricant. If

the compressor manufacturer's recommended lubrication rate is

exceeded, the desiccant bed can become contaminated with

compressor lubricants.

Periodically check the desiccant bed. If the tablets are discolored

(deep yellow or brown), the bed may be contaminated.

If the bed has become contaminated, it can be flushed with an

adequate supply of water. Depending upon the severity of

contamination, it might be necessary to completely flush the entire

bed from the dryer and replace it with new desiccant.

Check the compressor for proper operation. The compressor

might be worn or over lubricated. Check the compressor

operator's manual and correct.

Check the atmospheric air near the compressor air intake. Heavy

concentrations of acid fumes or smoke and dust will cause

contamination if they are drawn into the air system. Check or

install a filter on the compressor intake.

If it is not possible to reduce the amount of lubricants in the air

system, a separator and/or coalescing filter should be installed

before the dryer.

If the above check list does not remedy the problem, consult your local VAN AIR distributor or call

the VAN AIR factory in Lake City, Pennsylvania PHONE (814) 774-2631 or FAX (814) 774-

3482.