beautypg.com

Van Air Systems PD-2 Pressure Differential Gauge Kits User Manual

Pd-2, pd-2/sw, pd-2/ht, & pd-2/sw ht, Pressure differential gauge kits

background image

OCTOBER 2004

P/N 30-0602 REV A

INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

FOR

PD-2, PD-2/SW, PD-2/HT, & PD-2/SW HT

PRESSURE DIFFERENTIAL GAUGE KITS

RECOMMENDED FOR INSTALLATION ON F101 SERIES FILTERS

SPECIFICATIONS

INSTALLATION

WARNING

CAREFULLY READ THESE INSTRUC-
TIONS BEFORE INSTALLING THE
PRESSURE DIFFERENTIAL KIT.

MAKE SURE THAT THE COMPONENT
OR PIPING IS DEPRESSURIZED
BEFORE INSTALLING THE PRESSURE
DIFFERENTIAL KIT.

COMPLY WITH ALL APPLICABLE
ELECTRICAL CODES IF INSTALLING A
PD-2/SW OR PD-2/SW HT KIT.

Completely depressurize the piping and
component that the kit is to be installed on.

Figure 1 shows a typical assembly/installation
of the PD-2 series pressure differential gauge
on a VAN AIR F101 series filter housing.

Mount the gauge on the mounting bracket.
Use the fasteners provided with the kit. Mount
the kit to the desired surface.

IMPORTANT

To ensure an accurate reading, make
sure that both tubing lines to the
gauge are equal in length. Use as few
bends as possible in the tubing lines.

Install the necessary tubing from the inlet side
of the vessel or piping to be measured to the
HIGH PRESSURE port of the gauge. Use the
tubing and fittings as shown in FIGURE 1. Use
pipe sealant on all threaded pipe connections.

Complete the tubing connection from the outlet
side of the vessel or piping to be measured to
the LOW PRESSURE port of the gauge. Use
the tubing and fittings as shown in FIGURE 1.
Use pipe sealant on all threaded pipe connec-
tions.

SWITCH CONNECTIONS AND
ADJUSTMENTS (PD-2/SW PD-2/SW HT)

CONNECTING THE SWITCH

The gauges are equipped with an electric
switch. This switch can be used to activate

Disconnect the tubing from the HIGH
PRESSURE port on the gauge.

Using a clean, dryer source of compressed
air and a pressure regulator slowly apply
pressure to the HIGH PRESSURE port until
the gauge reads the desired set point.

Loosen the adjustment screw on the top of
the gauge. Use a voltmeter to check the
position of the switch. Slide the adjustment
screw until the switch is closed at the
desired pressure on the gauge. NOTE, The
screw may be difficult to slide. This is
normal.

Once the switch is properly set, tighten the
adjustment screw. Reconnect the sample
tubing to the HIGH PRESSURE port.

PD-2 KIT p/n 84-0129

MAX. OPERATING PRESSURE ..................... 200 PSIG
MAX. OPERATING TEMPERATURE .............. 150

O

F

OPERATING RANGE ...................................... 0-15 PSID
GAUGE DIMENSIONS..................... 4"L, 1.5"W, 2.0625"H
PRESSURE PORT CONNECTIONS .............. 1/8" NPT

PD-2/HT KIT p/n 84-0130 (Same as 84-0129 except)

MAX. OPERATING PRESSURE ..................... 3000 PSIG*
MAX. OPERATING TEMPERATURE ..............
175

O

F*

*NOTE: SEE F101 SERIES FILTER RATINGS.

PD-2/SW KIT p/n 84-0131

MAX. OPERATING PRESSURE ..................... 200 PSIG
MAX. OPERATING TEMPERATURE .............. 150

O

F

OPERATING RANGE ...................................... 0-15 PSID
GAUGE DIMENSIONS.....................4"L, 2.375"W, 3.75"H
PRESSURE PORT CONNECTIONS .............. 1/8" NPT
CONDUIT PORT CONNECTION ................... 1/2" NPT
SWITCH RATINGS

SET POINT (adjustable)0-15 PSID
ELECTRICAL ............... 110V/1PH/60Hz, 1/2 AMP, 50 WATTS
TYPE ............. SPST (Single Pole Single Throw)

an alarm to alert personnel that the
pressure differential across the measure
piping or vessel has reached an unaccept-
able level. The set point of the switch is
adjustable.

The valve is tapped with 1/2" NPT conduit
connections. Conduit can be run from the
gauge to the alarm panel.

Make the necessary wiring connections
from the gauge to the alarm panel.
Reference FIGURE 1.

ADJUSTING THE SWITCH SET POINT

The gauge switch is adjustable. It should
be set at the pressure differential reading
that you want to activate the alarm device.
If the gauge is installed on a filter set it at
the recommended element replacement
pressure differential, reference filter manual
for this setting.
Make sure that the piping or vessel that the
gauge is connected to is depressurized.

FIGURE 1 INSTALLATION

PD-2/SW HT KIT p/n 84-0211 (Same as 84-0131 except)

MAX. OPERATING PRESSURE ..................... 3000 PSIG
MAX. OPERATING TEMPERATURE .............. 175

O

F

MAINTENANCE: PER GAUGE INSTRUC-
TIONS.

WARRANTY: PER TERMS AND CONDI-
TIONS OF SALE.