Installation

513005

16

Do not modify the plug provided with the cord-kit - if

it will not fit the outlet, have a proper outlet installed

by a qualified electrician.
The dryer has its own terminal block that must be

connected to a separate branch, 60 Hertz, single phase

circuit, AC (alternating current) circuit, fused at 30

Amperes (the circuit must be fused on both sides of

the line). Electrical service for the dryer should be

of maximum rated voltage (208 or 240 Volt,

depending on heating element) listed on the

nameplate. Do not connect dryer to 110, 115, or 120

Volt circuit.

Heating elements are available for field installation in

dryers which are to be connected to electrical service

of different voltage than that listed on nameplate, such

as 208 Volt.

NOTE: Branch circuit wire size requirements to

laundry room outlet are shown in Table 4.

The power cord connection between wall receptacle

and dryer terminal block IS NOT supplied with

dryer. Type of power cord and gauge of wire must

conform to local codes.

Improper connection of the equipment-

grounding conductor can result in a risk of

electric shock. Check with a qualified

electrician or service person if you are in

doubt as to whether the dryer is properly

grounded.

W038

WARNING

Wire Length

Wire

Less than

15 ft. (4.5 m)

Listed No. 10 AWG

Copper wire only

Longer than

15 ft.(4.5 m)

Listed No. 8 AWG

Copper wire only

Table 4