INSTALLATION

A-1

RATED OUTPUT

OUTPUT

RECOMMEND INPUT WIRE AND FUSE SIZES

REQUIRED GAS FLOW RATE

REQUIRED GAS INLET PRESSURE

TECHNICAL SPECIFICATIONS - VIPER

Duty Cycle

50% Duty Cycle

100% Duty Cycle

Current

Range

25-60 Amps

Open Circuit

Voltage

MAX

335 VDC

For all plasma cutting applications Based on U.S. National Electrical Code

Ambient Temperature 30

o

C or Less

Pilot Current

18 Amps @ 100% Duty Cycle

AMPS

55
40

VOLTS

108
100

70 PSI @ 360 SCFH

( 4.8 Bar. @ 10160 LHR)

80 to 150 PSI

( 5.4 Bar. TO 10.2 Bar.)

THREE PHASE

SINGLE PHASE

RECOMMENDED INPUT WIRE AND FUSE SIZES

Type 75°C

Type 75°C

Copper

Fuse

Copper

Ground

(Superlag)

Wire in

Wire in

Input

or

Conduit

Conduit

Voltage

Breaker

AWG (IEC)

AWG (IEC)

Frequency

(1)

Size

Sizes

Sizes

208/50/60

40

10 (6mm

2

)

10 (6mm

2

)

230/50/60

40

10(6mm

2

)

10 (6mm

2

)

460/50/60

30

10 (6mm

2

)

10 (6mm

2

)

575/50/60

30

10 (6mm

2

)

10 (6mm

2

)

Type 75°C

Type 75°C

Copper

Fuse

Copper

Ground

(Superlag)

Wire in

Wire in

Input

or

Conduit

Conduit

Voltage

Breaker

AWG (IEC)

AWG (IEC)

Frequency

(1)

Size

Sizes

Sizes

208/50/60

80

8 (8.4mm

2

)

8 (8.4mm

2

)

230/50/60

80

8 (8.4mm

2

)

8 (8.4mm

2

)

460/50/60

40

10 (6mm

2

)

8 (8.4mm

2

)

Weight

Including Machine, Torch and

Torch Cable (Length)

(25ft/7.6m)

74 lbs.

34 kg.

PHYSICAL DIMENSIONS

Depth

26.0 in.

660 mm

Width

11.0 in.

280 mm

Height

12.6 in.

320 mm

(1) Input voltage must be within ±10% of rated value.

Standard

Input Current

Voltage

at Rated Output

Model

208/230/460

31/28/17

50/60 Hz

460/575

17/14

50/60 Hz

Standard

Input Current

Voltage

at Rated Output

Model

208/230/460

60/55/30

50/60Hz

INPUT

THREE PHASE

SINGLE PHASE