beautypg.com

Stuart Turner CH 4-30 B User Manual

Page 10

background image

- 10 -

Cont ...

2.30

Non-Preferred Pump Location: The pump must be located with at least 1 metre

flooded suction at all times.

If it is not possible to locate the pump in the preferred area due to site limitations

and it is necessary to position the unit in the loft, or in a position above the

secondary tapping that feeds the pump, then there is an increased risk of air

locks. This risk must be eliminated.

The following method will help to overcome the problem:

In this application only use an Essex or side entry flange, then fit a “U” bend or

downward loop in the supply pipe to the pump of 350 mm depth before rising to

the pump should ensure the cylinder vents its air up the expansion pipe, not up

the pump feed (Fig. 7).

Max. inlet head

10

m

Min. inlet head

1

m

350

mm

min.

Least preferred area

Fig. 7

This manual is related to the following products: