Hot water calculations and correction factor – Sterling VS User Manual

Page 12

background image

12

EXAMPLE: –

UNIT SIZE _______________________ 40

Entering

Water

Temp.

____________ 160°F

Entering

Air

Temp.

_______________ 40°F

Water

Temperature

Drop

__________ 10°F

I.

CAPACITY @ 20°F TD:

A. For 200°F EWT, 60°F EAT

Read output directly from Tables 7 & 8,

22,700 BTU/HR (Ref., Std. 40, p. 8).


B. For EWT and/or EAT above

Multiply output from Tables 7 & 8

or below Standard

by factor from Table 9 (below).

22,700 x .878 = 19,931 BTU/HR.

II. CAPACITY AT OTHER TD’s

Multiply output obtained in IA or IB

IA - 22,700 x 1.15 = 26,105 BTU/HR.

A. For TD’s from 5 to 60°F

(above) by appropriate factor from Table 10

– OR –

(below)

IB - 19,931 x 1.15 = 22,921 BTU/HR.

III. GPM AT OTHER TD’s

Multiply GPM of unit for 20°F TD, from Tables 7 & 8

2.34 x 2.30 = 5.38 GPM (Applies only to units with

A. For TD’s from 5 to 60°F

by appropriate factor from Table 10 (below).

Std. 200°F EWT, 60°F EAT) For all others calculate

BTU

using formula – GPM =

500 x TD

IV. PRESSURE LOSS AT OTHER TD’s

Multiply P.D. of unit for 20°F TD, from Tables 7 & 8

A.For TD’s from 5 to 60°F

by appropriate factor from Table 10 (below).

.06 x 5.00 = .30 Ft. H

2

O

367

1.10

(.069)

10 (6)

1.15

2.30

5.00

60 (33)

.72

.24

.07

280°

(138°)

1.850
1.755
1.663
1.571

1.483
1.397
1.311
1.230

260°

(127°)

1.702
1.609
1.518
1.429

1.342
1.257
1.173
1.094

240°

(116°)

1.555
1.464
1.375
1.286

1.201
1.117
1.035
0.955

220°

(104°)

1.408
1.317
1.231
1.143

1.060
0.977
0.897
0.818

200°

(93°)

1.268
1.172
1.085
1.000

0.918
0.837
0.759
0.682

180°

(82°)

1.120
1.025
0.941
0.857

0.777
0.698
0.621
0.546

160°

(71°)

0.963
0.878
0.796
0.715

0.636
0.558
0.483
0.409

140°

(60°)

0.814
0.731
0.651
0.571

0.494
0.419
0.345
0.273

120°

(49°)

0.666
0.585
0.506
0.429

0.353
0.279
0.207
0.137

100°

(38°)

0.518
0.439
0.361
0.286

0.212
0.140
0.069

0

300°

(149°)

1.997
1.908
1.824
1.717

1.630
1.545
1.462
1.371

30°

(-1)

40°

(4)

50°

(10)

60°

(16)

70°

(21)

80°

(27)

90°

(32)

100°

(38)

TABLE 9 — HOT WATER CONVERSION FACTORS BASED ON 200°F ENTERING WATER

60°F ENTERING AIR 20°F TEMPERATURE DROP

To obtain the BTU capacity for conditions other than those in the basic capacity tables, multiply the basic rating

(200°F entering water, 60°F entering air,) by the proper constant from the above tables.

TABLE 10 — HOT WATER BTU, GPM AND PRESSURE LOSS FACTORS BASED ON STANDARD

CONDITIONS OF 200°F ENTERING WATER 60°F ENTERING AIR & 20°F WATER DROP

UNIT SIZE

MIN.

GPM (L/s)

*TABLE 12 — HEATING CAPACITY FACTORS FOR VARIOUS RATES OF WATER FLOW

*TABLE 11 — MINIMUM WATER FLOW — GPM

ENTERING AIR

TEMPERATURE °F (°C)

ENTERING WATER TEMPERATURE — 20°F WATER TEMPERATURE DROP

TEMPERATURE DROP °F (°C)

USE FACTORS FROM THIS TABLE TO OBTAIN

APPROXIMATE RESULTS

To obtain BTU for other Water Temperature Drops,
multiply basic BTU rating by applicable Factor.

To obtain GPM for other Water Temperature Drops,
multiply basic GPM rating by applicable Factor.*

To obtain Pressure Loss Feet of Water for other
temperature Drops, multiply Basic loss at 20°F drop by
Factor.

175%

1.10

25%

.80

75%

.96

125%

1.04

150%

1.07

50%

.89

% of Rated Water Flow

Btu/Hr Heating Capacity

100%

1.00

40

.55

(.035)

62

.55

(.035)

77

.55

(.035)

104

.55

(.035)

144

.82

(.052)

164

.82

(.052)

200

1.10

(.069)

237

1.10

(.069)

317

1.10

(.069)

HOT WATER CALCULATIONS AND CORRECTION FACTOR

50 (28)

.76

.30

.13

40 (22)

.83

.40

.20

30 (17)

.90

.59

.40

20 (11)

1.00

1.00

1.00

25 (14)

.94

.74

.60

15 (8)

1.08

1.44

2.00

5 (3)

1.25

5.00

10.00