beautypg.com

Wiring the 4-wire rtd resistance input modules, Wiring the strain input modules • one-gauge method, One-gauge three-wire method – Yokogawa PC-Based MX100 User Manual

Page 6: Adjacent two-gauge method, Wiring procedure

background image

6

IM MX100-72E

• Wiring the 4-Wire RTD Resistance Input Modules

A

B

I

C

A

B

I

C

Votage

Nothing connected to the
I or C terminal

Resistance, RTD

+

Resistance per lead wire of 10 Ω or less

DC voltage
Input

Contact

A

B

b

I

+

• DC voltage input/DI (contact) input

• DC current input

• RTD input, resistance input

DC current input

Shunt resistor

Example: For 4 to 20 mA input, shut resistance values should be 250 Ω ±0.1%

Terminal type: Clamp
Applicable wire size: 0.14 to 1.5 mm

2

(AWG26 to 16)

• Wiring the Strain Input Modules

• One-Gauge Method

Setting switch

ON

OFF

No.1
No.2
No.3
No.4
No.5

A(+V)

B( L)

C(-V)

D( H)

-B12, -B35

-NDI

Rg

No.1

ON

No.2

ON

No.3

ON

No.4

OFF

No.5

OFF

Rg

Bridge head
(701955 or 701956)

Setting switch

R: fixed resistance
r: resistance value of lead wire
Rg: resistance value of strain gauge
e: output voltage from bridge
E: voltage applied to bridge

SW1

ON

SW2

ON

SW3

ON

SW4

ON

SW5

OFF

1 2 3 4 5

SW

Rg

1
2
3
4
5
6
7
8

ON

OFF

E

e

Rg

R

R

R

• One-Gauge Three-Wire Method

R: fixed

resistance

r:

resistance value of lead wire

Rg: resistance value of strain gauge
e: output voltage from bridge
E: voltage applied to bridge

ON

OFF

No.1

No.2
No.3
No.4
No.5

A(+V)

B(L)

C(-V)

D( H)

Rg

Setting switch

-B12, -B35

No.1

ON

No.2

ON

No.3

OFF

No.4

ON

No.5

OFF

-NDI

Bridge head
(701955 or 701956)

Setting switch

SW1

OFF

SW2

ON

SW3

ON

SW4

ON

SW5

OFF

1 2 3 4 5

SW

Rg

1
2
3
4
5
6
7
8

ON

OFF

R

R

R

Rg

r

r

r

E

e

• Adjacent Two-Gauge Method

Rg1

Rg2

Setting switch

ON

OFF

No.1
No.2
No.3
No.4
No.5

A(+V)

B( L)

C(-V)

D( H)

-B12, -B35

-NDI

No.1

ON

No.2

ON

No.3

OFF

No.4

OFF

No.5

ON

Rg1

Rg2

Bridge head
(701955 or 701956)

Setting switch

R: fixed resistance
r: resistance value of lead wire
Rg: resistance value of strain gauge
e: output voltage from bridge
E: voltage applied to bridge

SW1

OFF

SW2

ON

SW3

ON

SW4

ON

SW5

OFF

1 2 3 4 5

SW

Rg1

Rg2

1
2
3
4
5
6
7
8

ON

OFF

Rg1

Rg2

R

R

E

e

5. Wiring Procedure

This manual is related to the following products: