3.4 Test Procedures

Insulation Resistance

● Test Procedures

Perform a measurement with an insulation resistance meter and check whether the

results satisfy the reference values. Perform the measurement with the power switch
turned ON.

Reference Value

Terminals Measured

Reference Value

Condition

Between the power and protective ground

terminal

100 MΩ or more

Short the L (+) and N (–)

terminals.

Between the input and protective ground

terminal

100 MΩ or more

Short all input terminals.

Between the Ethernet and protective

ground terminal

100 MΩ or more

Short all pins of the Ethernet
terminal.

Between RS-422-A/485 SG and

RS-422-A/485 FG terminals

100 MΩ or more

With the /C3 option.

Protective Grounding

● Test Procedures

Perform a resistance measurement with a DMM (digital multimeter), and check

whether the results satisfy the reference values.

Reference Value

Measured Location

Reference Value

Between the protective ground terminal

and functional ground terminal

0.2 Ω or less

MV1000

Functional ground

terminal
Power inlet

Protective ground

terminal

Power supply

screw terminals