2Communication Command

The following commands related to messages, contact input, internal switch, and logic
computation are added (The contents that is different from standard specification are
described)

a)SG: Message character strings setting

Syntax SG p1, p2, p3

p1: Message group No. (1-30)
p2: Message No. (1-8)
p3: Message (16 alphanumeric characters)

b) MS: Message Write

Syntax MS p1, p2

p1: Message group No. (1-30)

p2: Message No. (1-8)

c) BG: Message group name

Syntax BG p1, p2

p1: message group number (1-30)

p2: group name (alphameric 16 characters)

d) GT: Contact input registration

Syntax GT p1, p2, p3

p3: Function type*1

*1:The followings are added.

Message number setting 0bit, message number setting 1bit,message number setting

2bits, Message number setting 3 bits,message number setting 4bits, message number

setting 5bits, Message number setting 6bits, message number setting 7bits,message

write

e) FL:

Outputs log, alarm summary, and message summary

Syntax FL p1, p2

Message summary output:

Group number and message number are described as three-digit number.

The first digit from the left and second digit in the center means group number.

The last digit in the right means message number.

For example: group number: 10, message number: 3

Æ103

f) MV: Logic computation setting

Syntax MV p1, p2, p3

p3: Equation (unnecessary when p2 is OFF, 120 characters)

-.SELECT()operator, 4 rules arithmetic can be used in logic computation

equation.