beautypg.com

2 message write with internal switch – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 16

background image

IM CX2000-S30E

14

4.2.2 Message Write with Internal Switch

Make the basic settings of message write function with internal switch.

Click the [Setup] tab then select the [DI/DO/SW-Regist] settings from the list that

appears on the left of the screen. Or, you can select the items by choosing [Control Settings] -

[Setup Mode]-[DI/DO/SW-Regist].

Figure 4.2.2 internal switch setting

In internal switch(INT-SW1 to INT-SW3), set message.

- Message number setting: 1, 1-3, 1-7, 1-31, 1-63, 1-127, 1-240

For example: in INT-SW

Message number 1:

Relay 1 SW001

Message number 1-3: Relay 2 SW001-SW002

Message number 1-7:

Relay 3 SW001-SW003

Message number 1-15: Relay 4 SW001-SW004

Message number 1-31: Relay 5 SW001-SW005

Message number 1-63: Relay 6 SW001-SW006

Message number 1-127: Relay 7 SW001-SW007

Message number 1-240: Relay 8 SW001-SW008