4 green series communication function expansion, Additional connecting mode (controllers) – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 7

background image

IM CX2000-S30E

5

1.4 Green Series Communication Function Expansion

Additional Connecting Mode (Controllers)

The external controllers kinds, of which parameters CX can auto-read are added as
follows. (The functions that CX supports UT series can be used.)

- Additional connecting kinds: US1000, UT100 series (UT130, UT150, UT152, and

UT155)

The following control modes and alarm kinds can be selected from CX.

US1000

- Control mode:

Single-loop control, Cascade-primary loop control, Cascade secondary-loop control, Cascade

control, Loop control for backup, Loop control with PV switching, Loop control with PV

auto-selector, Loop control with PV-hold function, Dual loop control, Temperature and Humidity

control, Cascade control with two universal inputs, Loop control with PV switching and two

universal inputs, Loop control with PV auto-selector and two universal inputs

- Alarm kinds (number of alarm: 4)

Off, PV high-limit alarm (energize), PV low-limit alarm (energize), Deviation high-limit alarm

(energize) Deviation low-limit alarm (energize), Deviation high-limit alarm (deenergize),

Deviation low-limit alarm (deenergize), Deviation high & low limit alarm (energize), Deviation

within high & low limits alarm (energize), PV high-limit alarm (deenergize), PV low-limit alarm

(deenergize), PV high-limit alarm (energize/hold), PV low-limit alarm (energize/hold)Deviation

high-limit alarm (energize/hold), Deviation low-limit alarm (energize/hold), Deviation high-limit

alarm (deenergize/hold), Deviation low-limit alarm (deenergize/hold), Deviation high & low limit

alarm (energize/hold), Deviation within high & low limits alarm (energize/hold), PV high-limit

alarm (deenergize/hold) , PV low-limit alarm (deenergize/hold), PV change-rate alarm

(energize), PV change-rate alarm (deenergize), Self-diagnosis alarm (energize),

Self-diagnosis alarm (deenergize), FAIL output, SP high-limit, SP low-limit SP-L, Output

high-limit, Output low-limit.

UT100 series

- Control mode: Single loop control

- Alarm kinds (number of alarm: 2)

Off, PV high-limit alarm (energize), PV low-limit alarm (energize), Deviation high-limit alarm

(energize) Deviation low-limit alarm (energize), Deviation high-limit alarm (deenergize),

Deviation low-limit alarm (deenergize), Deviation high & low limit alarm (energize), Deviation

within high & low limits alarm (energize), PV high-limit alarm (deenergize), PV low-limit alarm

(deenergize), PV high-limit alarm (energize/hold), PV low-limit alarm (energize/hold)Deviation

high-limit alarm (energize/hold), Deviation low-limit alarm (energize/hold), Deviation high-limit

alarm (deenergize/hold), Deviation low-limit alarm (deenergize/hold), Deviation high & low

limit alarm (energize/hold), Deviation within high & low limits alarm (energize/hold), PV

high-limit alarm (deenergize/hold) , PV low-limit alarm (deenergize/hold), Self-diagnosis

output, FAIL output, Timer function, Timer function (deenergize), Heater burn out alarm