7.2 WIRING DESIGNATIONS FOR THE MODEL 415
Terminal
Model 415R
Model 415A
1
Calibration Link
Calibration Link
2
Signal Ground
Signal Ground
3
Flow 1 (4-20mA)
Flow 1 (4-20mA)
4
PT100 I (+)
Temperature (4-20mA)
5
PT100 Signal (+)
Reset Switch
6
PT100 Signal (-)
Display Switch
7
Pressure (4-20mA)
Pressure (4-20mA)
8
Flow Common (-)
Flow Common (-)
9
Flow Pulse Input (+)
Flow Pulse Input (+)
10
Pulse Out
Pulse Out
11
DC Power Out (8-24V)
DC Power Out (8-24V)
12
DC Ground
DC Ground
13
DC Power Input
DC Power Input
14
PT100 I (-)
Flow 2 (4-20mA)
Note:
When using a single 4-20mA flowmeter, it is connected to
terminal 3. The second 4-20mA flow input on terminal 14 is only
used when there are dual 4-20mA inputs. In this case, terminal 3
becomes the High Flow input and terminal 14 is used for the low
flow.
Terminal
Analog Flow Output (4-20mA)
RS232/422/485
20
Not To Be Used
RS232 Signal Ground
21
0 Volts
RS232 Data In
22
0-10 Volts
RS232 Data Out
23
-12 Volts
RS422/485 (-) Data Out
24
I(-)
RS422/485 (+) Data Out
25
I(+)
RS422/485 (-) Data In
26
+15 Volts
RS422/485 (+) Data In
27
Not To Be Used
RS232 CTS
Installation 73