Specifications
Analog Inputs
Sensor input channels: 8
Sensor Types and Trip Point Ranges:
• 2-Wire 100 Ω Platinum RTD DIN curve (385): -100 to
850°C (-148 to 1,562°F)
• E Thermocouple: 100 to 801°C (212 to 1,474°F)
• K Thermocouple: 100 to 1,205°C (212 to 2,201°F)
• S Thermocouple: 500 to 1,711°C (932 to 3,112°F)
• J Thermocouple: 100 to 754°C (212 to 1,389°F)
• R Thermocouple: 500 to 1,720°C (932 to 3,128°F)
• T Thermocouple: 100 to 384°C (212 to 723°F)
• Thermostatic switch
At actual temperatures of -100°C (-148°F) or less, nuisance
alarms may occur.
Accuracy for trip points above 100°C (212°F):
• For part numbers starting with “TLME,” ± 5% of trip
point.
• For part numbers starting with “TLMC,” see below.
Sensor (s)
Trip Point Accuracy
Ambient: 15 to 35ºC
(59 to 95ºF)
Trip Point Accuracy
Ambient: 0 to 60ºC
(32 to 140ºF)
J, K, E, T, RTD
±0.5% of trip point and
±2ºC (3.2ºF)
±0.5% of trip point and
±4ºC (7.2ºF)
S, R
±0.5% of trip point and
±3ºC (5.4ºF)
±0.5% of trip point and
±5ºC (9ºF)
Repeatability: better than 5°C (9°F) or accuracy for trip
point, whichever is less.
Input filter: 1 second (minimum time the over-temperature
condition exists before the output responds)
Isolation:
• Common Mode: ± 10V
Å
(ac) or VÎ (dc)
(Input to analog common)
• Input-to-Input: ± 10V
Å
(ac) or VÎ (dc)
• Input-to-Frame Ground: ± 500V
Å
(ac) or VÎ (dc)
ACK Input
Function: alarm acknowledge
Type: digital input
Activation: edge triggered (on to off transition)
Filter: 20 milliseconds
Maximum time to reset relays: 3.5 seconds
Maximum time signal should be held high: 5 seconds
Isolation: optical
Voltage and current: 5 to 30VÎ (dc); 2 mA @ 5VÎ (dc); 19
mA @ 30VÎ (dc)
Impedance: 1.5 kΩ
TST Input
Function: test
Type: digital input
Activation: level triggered (signal high)
Filter: must be active for 1 second for valid simulation
Maximum time signal should be held high: 5 seconds
Isolation: optical
Voltage and current: 5 to 30VÎ (dc); 2 mA @ 5VÎ (dc); 19
mA @ 30VÎ (dc)
Impedance: 1.5 kΩ
Electromechanical Alarm Relays
Contact arrangement: open in power-off condition
Contact action: latch open in alarm condition
Maximum contact rating: 1 A @ 30VÎ (dc)
Indicator Lights
Alarm status: 8 red
Power: 1 green
Dimensions
Length: 236 mm (9.30 in.)
Width: 92 mm (3.61 in.)
Depth: 48 mm (1.87 in.)
DIN rail mount: add 20 mm (0.75 in.) to depth
Power Requirements
Nominal voltage: 12 to 24V
Î
(dc)
Absolute voltage: 10 to 27V
Î
(dc)
Power: 3.2 watts
Requires: Class 2 power supply
Terminal Blocks
Type: Removable
Torque: 0.33 to 0.35 Nm (2.9 to 3.1 in-lbs.)
Wire Gauge: 26 to 18 AWG
Environmental
Operating ambient temperature: 0 to 60°C (32 to 140°F)
Storage ambient temperature: -20 to 100°C (-4 to 212°F)
Relative humidity: 0 to 95%, non condensing
Agency Approvals / Compliance
UL, cUL Listed (File No. E185611)
• Process Control Equipment UL 61010
• Process Control Equipment C22.2 #61010-1
FM
• Temperature Limit Switches – Non Indicating Class 3545
• Temperature Supervisory Switch Class 3545
CE
• Low Voltage Directive (LVD) 73/23/EEC
• Electromagnetic Compatibility Directive (EMC) 2004/108/
EC