6

WATLOW TLM-8 User’s Guide

Specifications

Analog Inputs

Sensor input channels: 8

Sensor Types and Trip Point Ranges:

• 2-Wire 100 Ω Platinum RTD DIN curve (385): -100 to

850°C (-148 to 1,562°F)

• E Thermocouple: 100 to 801°C (212 to 1,474°F)

• K Thermocouple: 100 to 1,205°C (212 to 2,201°F)

• S Thermocouple: 500 to 1,711°C (932 to 3,112°F)

• J Thermocouple: 100 to 754°C (212 to 1,389°F)

• R Thermocouple: 500 to 1,720°C (932 to 3,128°F)

• T Thermocouple: 100 to 384°C (212 to 723°F)

• Thermostatic switch

At actual temperatures of -100°C (-148°F) or less, nuisance

alarms may occur.

Accuracy for trip points above 100°C (212°F):

• For part numbers starting with “TLME,” ± 5% of trip

point.

• For part numbers starting with “TLMC,” see below.

Sensor (s)

Trip Point Accuracy

Ambient: 15 to 35ºC

(59 to 95ºF)

Trip Point Accuracy

Ambient: 0 to 60ºC

(32 to 140ºF)

J, K, E, T, RTD

±0.5% of trip point and
±2ºC (3.2ºF)

±0.5% of trip point and
±4ºC (7.2ºF)

S, R

±0.5% of trip point and
±3ºC (5.4ºF)

±0.5% of trip point and
±5ºC (9ºF)

Repeatability: better than 5°C (9°F) or accuracy for trip

point, whichever is less.

Input filter: 1 second (minimum time the over-temperature

condition exists before the output responds)

Isolation:

• Common Mode: ± 10V

Å

(ac) or VÎ (dc)

(Input to analog common)

• Input-to-Input: ± 10V

Å

(ac) or VÎ (dc)

• Input-to-Frame Ground: ± 500V

Å

(ac) or VÎ (dc)

ACK Input

Function: alarm acknowledge

Type: digital input

Activation: edge triggered (on to off transition)

Filter: 20 milliseconds

Maximum time to reset relays: 3.5 seconds

Maximum time signal should be held high: 5 seconds

Isolation: optical

Voltage and current: 5 to 30VÎ (dc); 2 mA @ 5VÎ (dc); 19

mA @ 30VÎ (dc)

Impedance: 1.5 kΩ

TST Input

Function: test

Type: digital input

Activation: level triggered (signal high)

Filter: must be active for 1 second for valid simulation

Maximum time signal should be held high: 5 seconds

Isolation: optical

Voltage and current: 5 to 30VÎ (dc); 2 mA @ 5VÎ (dc); 19

mA @ 30VÎ (dc)

Impedance: 1.5 kΩ

Electromechanical Alarm Relays

Contact arrangement: open in power-off condition

Contact action: latch open in alarm condition

Maximum contact rating: 1 A @ 30VÎ (dc)

Indicator Lights

Alarm status: 8 red

Power: 1 green

Dimensions

Length: 236 mm (9.30 in.)

Width: 92 mm (3.61 in.)

Depth: 48 mm (1.87 in.)

DIN rail mount: add 20 mm (0.75 in.) to depth

Power Requirements

Nominal voltage: 12 to 24V

Î

(dc)

Absolute voltage: 10 to 27V

Î

(dc)

Power: 3.2 watts

Requires: Class 2 power supply

Terminal Blocks

Type: Removable

Torque: 0.33 to 0.35 Nm (2.9 to 3.1 in-lbs.)

Wire Gauge: 26 to 18 AWG

Environmental

Operating ambient temperature: 0 to 60°C (32 to 140°F)

Storage ambient temperature: -20 to 100°C (-4 to 212°F)

Relative humidity: 0 to 95%, non condensing

Agency Approvals / Compliance

UL, cUL Listed (File No. E185611)

• Process Control Equipment UL 61010

• Process Control Equipment C22.2 #61010-1

FM

• Temperature Limit Switches – Non Indicating Class 3545

• Temperature Supervisory Switch Class 3545

CE

• Low Voltage Directive (LVD) 73/23/EEC

• Electromagnetic Compatibility Directive (EMC) 2004/108/

EC