Watlow Silver Series OIT Installation Guide
0600-0069-0000 Rev D
Control Panel Design Guidelines
Pay careful attention to the placement of system components and 
associated cable routing. These items can significantly enhance the 
performance and integrity of your control application. 
 
Figure 1:  Typical Panel Layout 
 
Control Panel Grounding
The control panel must be connected to a good, high-integrity earth 
ground both for safety considerations and shielding purposes. Maple 
Systems cannot overemphasize the importance of good grounding. If 
you fail to use good grounding procedures during installation, sporadic 
malfunction of the OIT may occur: 
-
Connect the OITs chassis ground terminal to a reliable earth 
ground with a low-resistance path. 
-
Route all earth ground wires that lead from the OIT, the PLC, the 
power supply, and the line filter to a central earth ground point 
such as a barrier strip. This will ensure that no ground current 
from one device influences the operation of the other devices. 
-
Connect the OIT chassis ground terminal to the control panel 
door using a heavy-gauge short braided cable or ground wire to 
minimize resistance. 
-
Connect the power cable’s shield wire to the OIT’s chassis 
ground terminal. 