beautypg.com

Watlow Series EHG CL User Manual

Page 5

background image

Watlow Controls

5

EHG CL User’s Guide

EHG CL Error Codes (cont.)

Display

Description Possible

Cause

Corrective

Action

[Ahi]

Alarm High

Process temp exceeds set point by
value greater than alarm high setting

Set HTA value to correct high
temperature alert value

[Alo]

Alarm Low

Process temp below set point by value
greater than alarm low setting

Set LTA value to correct Low
temperature alert value

[E91]

Communications Queue
Full

Communications buffer overfl ow

Contact Technical Support at
1-507-494-5656

[E10]

EEPROM Error

EEPROM memory space fails CRC
check (checksum for parameter space)

Contact Technical Support at
1-507-494-5656

[E11]

CRC Error

Flash memory space fails CRC check
(checksum for program space)

Contact Technical Support at
1-507-494-5656

[E12]

CPU Clock Error

Clock frequency is < 5 MHz or > 13.1
MHz

Contact Technical Support at
1-507-494-5656

[E13]

Stack Overfl ow

Stack has overfl owed

Contact Technical Support at
1-507-494-5656

[E15]

AI Function Error

Analog reference is < 1.82 or > 2.06
volts

Contact Technical Support at
1-507-494-5656

[E16]

Process Comparison
Error

Limit and control sensor readings
differ by value greater than process
comparison value

Check setting of Proces Com-
parison Value

Set Process Comparison Value
to correct value

Check wiring of sensors

[E17]

Data Store Error

Data store functions are not set up

Check setting of Process Com-
parison Value

Check wiring of sensors

[E20]

Base control fi rmware
ID not supported

Base control fi rmware is not compat-
ible with Display Module fi rmware

• Check

fi rmware compatibility

between Base Control and
Display Module.

Revision 20.0

and greater for Base Control
and Display Module are com-
patible for EHG2-AAAA-0000

.