Keys and indicator lights, Watlow controls 4 ehg cl user’s guide, Ehg cl error codes – Watlow Series EHG CL User Manual

Page 4

background image

Watlow Controls

4

EHG CL User’s Guide

Alarm (flashing red)
Indicates that the process
temperature is higher than the
Limit High Set Point.
Alert (solid red)
Indicates that the process
temperature is higher than the
Closed Loop Set Point plus the

High Temperature Alert
Value

.

Output (green)
Indicates that the output is on.

In Range (solid yellow)
Indicates that the process
temperature is in the normal
operating range (see figure at
right).

Up-Arrow Key

Increases the

displayed value.

Down-Arrow Key

Decreases the

displayed value.

Mode Key

Toggles the display between

the set point and process

temperature. Enters edited

values and advances

to the next prompt.

Optional Communications

Connectors

Optional Communications

Connectors

Flashing
Alert/Alarm
(red) and
In Range (yellow)

If they are flashing together, that
indicates an Ambient Alarm
(controller temperature higher
than 85°C).

If they are flashing alternately, that
indicates a Health Check Error.

Alert/Alarm

In Range

Output

Alert/Alarm

In Range

Output

Alert/Alarm

In Range

Output

Alert/Alarm

In Range

Output

Alert/Alarm

In Range

Output

Alert/Alarm

In Range

Output

Alert/Alarm

In Range

Output

flashing

flashing

alternate
flashing

Control

Relay

Temperature

Alert Signal

off

off

off

on

off

on

on

on

off

off Ambient Alarm

[Abt] 85°C

on

on

off

off Health Check Error

Normal Operating Range

Limit High Set Point

[SLA]

Closed Loop Set Point

Closed Loop Set Point

T

emper

atur

e

Alarm Hysteresis

Alarm Hysteresis

On-Off Hysteresis

[HyS]

Closed Loop Set Point

Keys and Indicator Lights

EHG CL Error Codes

Display

Description Possible

Cause

Corrective

Action

Flashing

888

Limit error

Sensor has exceeded SLA value or
open thermocouple

Set SLA to correct Safety
Limit Value

Check wiring of sensor

Check sensor confi guration

Flashing

888

Control error

Sensor has exceeded SLA value or
open thermocouple

Set SLA to correct Safety
Limit Value

Check wiring of sensor

Check sensor confi guration

[Er3]

Limit Sensor Error

Limit sensor reading out of range (<
-13 or > 640)

Check wiring of sensor

Check sensor confi guration

[Er4]

Control Sensor Error

Control sensor reading out of range
(<-13 or > 640)

Check wiring of sensor

Check sensor confi guration

[Er5]

Limit Ambient Error

Temperature at limit sensor cold junc-
tion (> 185 degrees)

Check to be certain the EHG
CL is not in an ambient condi-
tion greater than 185 degrees
C

[Er6]

Control Ambient Error

Temperature at control cold junction
(> 185 degrees)

Check to be certain the EHG
CL is not in an ambient condi-
tion greater than 185 degrees
C

[ER9]

HMI Communications
Fault

Loss of communication between base
and display communications module.
See Also E20.

Check connection between
EHG CL and display/commu-
nications module