Watlow Controls

2

EHG CL User’s Guide

Navigating the Series EHG CL with the Front Panel

The three-character display normally shows the process
temperature. To view and change the existing Set Point
value follow the steps below:

1. Press the Mode Key once. The right decimal point

will illuminate when viewing the Set Point value.

2. Press the Up-Arrow or Down-Arrow Key to change

the Set Point.

3. Press the Mode Key again to return to the process

temperature display.

The display will automatically return to showing the
process temperature after three seconds.

To view or change parameter values follow the steps
below:

1. Hold down both the Up-Arrow and Down-Arrow Keys

for five seconds.

This will display the Set Point High Limit prompt.

2. Press the Mode Key to view the other parameter

prompts.

3. Press the Up-Arrow or Down-Arrow Key once to view

a parameter’s value.

4. Press the Up-Arrow or Down-Arrow Key to increase

or decrease that value.

5. Press the Mode Key to again display the prompt and

again to display the next prompt.

6. Press the Mode Key at the Display Build Number

prompt to return to the process value display.

Display

Parameter Name & Description

Range

Default

Modbus
Relative

Address

Data Type

& Read/

Write

Numeric

Process Value Controller

View the present Process Value.

-18 to 537°C (0 to 999°F)

20°C (68°F)

20

unsigned
integer

R

Numeric

Closed Loop Set Point

Set the set point that the controller
will automatically control to.

0°C (32°F) to SLA setting

150°C (302°F)

34

unsigned
integer

RWE

No Dis-
play

Heat Output Power

Read (via Modbus communications)
the present heat output power level.

0 to 100%

0

22

unsigned
integer

R

No Dis-
play

Alert Status

Read (via Modbus communications)
the present alert status.

Alert Low (7)

Alert High (8)

Alert None (6)

Alert None

31

unsigned
integer

R

No Dis-
play

Process Comparison Value

Set or read (via Modbus communica-
tions) the Process Comparison Value.

5 to 50°C (9 to 90°F)

20°C (68°F)

68

unsigned
integer

RWE

No Dis-
play

Limit Status

Read (via Modbus communications)
the present condition of the limit.

Bit 5 (0x0020)

0 = Not tripped (process value below

limit high set point)

1 = Tripped (process value exceeds

limit high set point)

0

63

unsigned
integer

R

No Dis-
play

Controller Sensor Status

Read (via Modbus communications)
the present status of the controller
sensor.

Bit 2 (0x0004)

0 = Good

1 = Failure

0

23

unsigned
integer

R

No Dis-
play

Limit Sensor Value

View the present value of the limit
sensor.

-18 to 537°C (0 to 999°F)

20°C (68°F)

60

unsigned
integer

R

[SLA]
[SLA]

Limit High Set Point

Set the high process value that will
trigger the limit.

0 to 438°C (32 to 820°F)

200°C (392°F)

33

unsigned
integer

RWE

[Cnt]
[Cnt]

Control Mode Select

Select a control method.

[onF]

On-Off (2)

[PId]

PID (3)

on-off

42

unsigned
integer

RWE

Note:

All values above 999 will be rounded off to fit in the three-character display. Full values can be

read with other interfaces.

Note:

The EHG CL does not support Modbus function code 16 (0x10) Write Multiple Registers. Pa-
rameter values must be written individually with function code 6 (0x06) Write Single Registers.

R: Read
W: Write
E: EEPROM