WATLOW Series 945 High/Low Limit User's Manual

Operation Parameters

Value

Range

Factory Default

Target Set Point

See explanation above.

ALO-

Deviation dE

-999

°

to 0

°

-999

Process Pr

rL to AHI

rL

AHI-

Deviation dE

0

°

to 999

°

999

°

Process Pr

ALO to rH

rH

OFF

±

180

°

F /

±

100

°

C

0

Figure 15 -
The Operation Menu.

NOTE:

The Upper display
will always return to
the process value
after 1 minute
without key strokes.

ALO

AHI

OFF

Table 3 -
Operation Menu
Prompts and
Descriptions.

Operation Menu

Use this page as a master copy for your Series 945 Operation Parameters.
Do not enter any values here; make photocopies instead.

Target Set Point or Blank: Displays the target set point while using deviation
alarm only. Display remains blank while in the process alarm mode.

Alarm Low: This parameter represents the low process alarm or low deviation
alarm for the mechanical relay alarms.
Range: 0 to -999

°

F/0 to -999

°

C/0 to -999 Units Default: -999

°

F

If AtyP = Pr:

Range: rL to AHI

Default: rL

Alarm High: This parameter represents the high process alarm or high
deviation alarm for the mechanical relay alarms.
Range: 0 to 999

°

F/0 to 999

°

C/0 to 999 Units

Default: 999

°

F

If AtyP = Pr:

Range: ALO to rH

Default: rH

Calibration Offset: Adds or subtracts degrees from the input signal.
Range:

±

180

°

F /

±

100

°

C

Default: 0

Operation Parameters

M

ACt

ALO

AHI

CAL

( )

( )

( )

Represents target set point
for deviation alarms, or
remains blank

Mode Key

Operation

OFF