WATLOW Series 945 High/Low Limit User's Manual

Setup

Lock: Selects the level of operator lock-out.
Range: 0 - 2

Default: 0

The levels of operator lock-out are defined as follows:
LOC 0: All operating parameters may be viewed or changed.

LOC 1: No calibration offset adjustments permitted.

LOC 2: No adjustments permitted.

Input: Selects the sensor input type. Only those input types which are compat-
ible with your unit will appear. See the model number information for your type.
Range: J, K (appears as H), t, n, c, Pt2, rtd, rt.d, 0-5, 420

Default: t

Decimal: Selects the location of the decimal point for all process related data.
This parameter only appears if the In parameter is 0-5 or 420.
Range: 0, 0.0, 0.00

Default: 0

Celsius _ Fahrenheit: Selects the units of temperature measurement for the
control. This parameter only appears if the In parameter is a thermocouple or
RTD input selection.

Range: C or F

Default: F

Range Low: Selects the low limit of the process alarm set point and the devia-
tion alarm target set point. See Table 1 on Page 11 for range values.
Range: Sensor range low to rH

Default: Low limit of sensor type

Range High: Selects the high limit of the process alarm set point and the
deviation alarm target set point. See Table 1 on Page 11 for range values.
Range: Sensor range high to rL

Default: High limit of sensor type

Alarm 2 Type: Determines whether the Alarm 2 Outputs are a process or
deviation alarm. A process alarm is set at an absolute temperature to prevent
over/underrange.

Range: Pr or dE

Default: Pr

Latching : Selects whether Alarm 2 Outputs are latching or non-latching.
Latching must be cleared before the alarm output will reset. Non-latching auto-
matically resets the alarm output when the condition clears.
Range: LAt or nLA

Default: LAt

Hysteresis: Selects the switching hysteresis for Alarm 1 and Alarm 2.
Range:

1

°

F - 99

°

F

0.1

°

F - 9.9

°

F

Default: 3

°

F

1

°

C - 55

°

C

0.1

°

C - 5.5

°

C

1Unit - 99 Units

0.1 Units - 9.9 Units

RTD: Selects the RTD calibration curve for RTD inputs. This parameter will not
appear unless In = rtd or rt.d. JIS = 0.003916

/

Ω°

C, DIN = 0.003850

/

Ω°

C.

Range: din or JIS

Default: DIN

Baud: Represents the baud rate the serial communications is running at.
Appears if your 945 has communications.
Range: 300, 600, 1200, 2400, 4800, 9600

Default: 1200

Data: Allows the user to select the data bits and parity for communication. This
parameter will appear if your Series 945 has communications.
Range: 7 o = 7 data bits and odd parity

Default: 7 o

7 E = 7 data bits and even parity
8 n = 8 Data bits and no parity