Rtd calibration – Watlow Series 365 User Manual

Page 12

background image

12

WATLOW Series 365 User’s Manual

RTD Calibration

The Series 365 is calibrated and tested before leaving the factory.

RTD Calibration

365X-X1XX-X000

Equipment required:

1K

Decade Box

Setup:
1.

Wire your control for the correct line voltage. See power wiring on
Page 6, Figure 6.

2.

Connect the decade box to the S1 and S2 terminals on the Series 365
(Terminals 2 and 3). See Page 7, Figure 9.

3.

Make sure the heat/cool switch is in the correct position for your application.
See Page 6, Figure 5. Apply power.

4.

Refer to Table 2 below for values that apply to your unit’s range code.

Procedure:
1.

Set the decade box to ______ , the Low
Ohms value. Turn the setpot fully CCW.
Adjust the Low pot until the unit just fully
de-energizes.

2.

Set thedecade box to ______, the High
Ohms value. Turn the setpot fully CW.
Adjust the High pot until the unit just fully
de-energizes.

3.

Repeat Steps 1 and 2 as necessary until
no further adjustment is needed.

Range

Ohms

Code

Low/High

RTD

Low

High

Curve

Ohms

Ohms

101

-328

to 1112°F

DIN

18.49

313.59

102

-328

to 1112°F

JIS

17.14

317.28

Bottom View

High

Potentiometer

Low

Potentiometer

Table 2 -
RTD Input
Calibration Values