WATLOW Series 365 User’s Manual

11

T/C Calibration

The Series 365 is calibrated and tested before leaving the factory.

Thermocouple Calibration

365X-X6XX-X000

Equipment required:

Precision millivolt source (mV source).

Appropriate type reference compensator with reference junction at 32°F/0°C.

Setup:
1.

Wire your control for the correct line voltage. See power wiring on
Page 6, Figure 6.

2.

Connect the millivolt source to the thermocouple reference compensator, and
the compensator to the thermocouple input terminals on the Series 365
(Terminals 3 and 5). See Page 7, Figure 8.

3.

Make sure the heat/cool switch is in the correct position for your application.
See Page 6, Figure 5. Apply power.

4.

Refer to Table 1 below for values that apply to your unit’s range code.

Range

Millivolt

Code

Low/High

T/C

Low

High

Type

mV

mV

601

32 to

600°F/

0 to

315°C

“J”

0.000

17.186

602

32 to 1382°F/

0 to

750°C

“J”

0.000

42.283

603

32 to 2282°F/

0 to 1250°C

“K”

0.000

50.633

604

150 to

662°F/

66 to

350°C

“T”

3.711

17.816

605

-328 to

150°F/ -200 to

66°C

“T”

-5.603

2.711

606

32 to 2543°F/

0 to 1395°C

“Pt2”

0.000

55.246

607

32 to 2732°F/

0 to 1500°C

“S”

0.000

15.576

608

32 to 2732°F/

0 to 1500°C

“R”

0.000

17.445

Procedure:
1.

Set the mV source to ______, the Low mV
value. Turn the setpot fully CCW. Adjust the
Low pot until the unit just fully de-energizes.

2.

Set the mV source to ______, the High mV
value. Turn the setpot fully CW. Adjust the
High pot until the unit just fully de-energizes.

3.

Repeat Steps 1 and 2 as necessary until no
further adjustment is needed.

Bottom View

High

Potentiometer

Low

Potentiometer

Table 1 -
Thermocouple Input
Calibration Values