Specifications

2

WATLOW DIN-A-MITE Style D User’s Manual

Operator Interface

Command signal input and indication light

Alarm output and indication light

Amperage

Single-phase, 80A output maximum at 50°C (122°F) into a resistive
load. See the Output Rating Curve chart on page 3.

Maximum surge current for 16.6 milliseconds, 1,800-amp peak

Maximum I

2

t for fusing: 16,200 A

2

sec

Latching current: 500mA minimum

Holding current: 200mA minimum

Off-state leakage: 1mA at 25°C (77°F) maximum

• 200KA SCCR type 1 and 2 approved with the recommended fusing

(see page 3)

Line Voltage

24 to 48VÅ (ac) units: 20 minimum to 53VÅ (ac) maximum

120 to 240VÅ (ac) units: 48 minimum to 265VÅ (ac) maximum

277 to 480VÅ (ac) units: 85 minimum to 528VÅ (ac) maximum

277 to 600VÅ (ac) units: 85 minimum to 660VÅ (ac) maximum

50/60 Hz independent +/- 5%

Control Mode, Zero Cross

Input Control Signal Type C: VÎ (dc) input contactor. To increase
service life, the cycle time should be less than three seconds.

Input Control Signal Type K: VÅ (ac) input contactor. To increase
service life, the cycle time should be less than three seconds.

Input Control Signal Type F: 4 to 20mAÎ (dc) variable time base
control

Input Command Signal

AC contactor
24VÅ ±10%, 120VÅ +10% / -25%, 240VÅ (ac) +10% / -25% @ 25mA
maximum per controlled leg

Do not use the DIN-A-MITE Vac-input models with a temperature
controller that includes an RC snubber circuit across its output.
Remove the RC snubber circuit before placing the DIN-A-MITE into
service.

DC Contactor
4.5VÎ to 32VÎ (dc): maximum current @ 4.5VÎ (dc) is 6mA per leg.
Add 3mA if alarm option is included

Loop powered linear current
4mAÎ to 20mAÎ (dc): loop-powered. Input Type F0 and F1 options
only. (Requires current source with 6.2VÎ (dc) available. No more
than three DIN-A-MITE inputs connected in series)

Linearity (Input Control Signal Type F)
• Full on point 19.5 to 19.9mAÎ (dc), maximum voltage of 6.2V peak.
• ±5% input to output power accuracy, 0% to 100% of span (4.3 to

19.7mA or 12.3 to 19.7mA).

• Temperature stability is less than 0.15%/°C change.

Alarm

Shorted SCR Alarm Option

Alarm state when the input command signal off and a 15A or more
load current is detected by the current transformer.

Alarm Output

Energizes on alarm, non-latching

Triac 24 to 240VÅ (ac) external supply with a current rating of 300mA
@ 25°C (77°F), 200mA @ 50°C (122°F), 100mA @ 80°C (176°F) and
a holding current of 200 µA with a latching current of 5mA typical

Current Sensing

On-board current transformer (CT), typically 0.2VÅ (ac) output signal
per ampere sensed

Agency Approvals

CE with proper filter:
2004/108/EC Electromagnetic Compatibility Directive
EN 61326: Industrial Immunity Class A emissions
Not suitable for Class B emissions environment
2006/95/EC Low Voltage Directive
EN 50178 Safety Requirements

UL® 508-listed and C-UL® File E73741

Input Terminals

Compression: Will accept 0.13 to 3.3 mm

2

(26 to 12 AWG) wire

Torque to 0.5 Nm (4.4 in-lb) maximum with a 3.5 mm (1/8 in) blade
screwdriver

Wire strip length 7 mm (0.28 in)

Line and Load Terminals

Compression: Will accept 13.3 to 34 mm

2

(6 to 2 AWG) wire

Torque to 9.0 to 10.1 Nm (80 to 90 in-lb) maximum with a 3/16 inch
Allen head

Wire strip length 17.5 mm (0.69 in)

Operating Environment

Operating temperature range: 0 to 85°C (32°F to 185°F)

0 to 90% RH (relative humidity), non-condensing

Vibration: 2 g, 10 Hz to 150 Hz, applied in any one of three axes

Storage temperature: -40 to 85°C (-40°F to 185°F)

Insulation tested to 3,000 meters

Installation Category III, pollution degree 2

Mounting

Standard back panel mounting; fits the same mounting pattern as a
100 A, single-phase mercury displacement relay

Mounting holes offer clearance for an M5 (No. 10) screw

On-board semiconductor fusing, Bussmann part number 170N3437

Dimensions

Height: 185 mm (7.28 in)

Width: 66 mm (2.58 in)

Depth: 239 mm (9.41 in)

Weight: 2.9 kg (6.3 lb)

Specifications are subject to change without notice.