Troubleshooting, Caution – Lincoln Electric IM10122 SAE400 User Manual

Page 26

background image

E-5

TROUBLESHOOTING

E-5

SAE-400

®

Observe all Safety Guidelines detailed throughout this manual

If for any reason you do not understand the test procedures or are unable to perform the tests/repairs safely, contact your Local
Lincoln Authorized Field Service Facility
for technical troubleshooting assistance before you proceed.

CAUTION

FUNCTION PROBLEMS

PROBLEMS

(SYMPTOMS)

POSSIBLE

CAUSE

RECOMMENDED

COURSE OF ACTION

No auxiliary power

1. Circuit Breakers open.

2. Faulty connections to auxiliary

receptacles.

3. RCD tripped.

1.

Check and reset breakers. If
breakers keep tripping check con-
nections to auxiliary receptacles.
Also make sure load does nor
exceed receptacleʼs current rating.

2. Check connections.

3. Clear any ground fault and reset

RCD circuit by pressing “Reset”
button.