beautypg.com

Operation – Lincoln Electric IM10027 SAE400 User Manual

Page 16

background image

B-4

OPERATION

B-4

AUXILIARY POWER CONTROLS

115 VAC Receptacle

One 20 amp, 115VAC (5-20R) NEMA duplex recepta-
cle provides 115VAC for auxiliary power. Maximum
current is 20 amps total.

One 115V (European IEC-309) 16 amp receptacle. IP44
rated.

230VAC Receptacle

One 15 amp, 230VAC duplex receptacle provides 230
VAC for auxiliary power. A total of 13 amps can be
drawn from this receptacle.

One 230V (European IEC-309) 15 amp receptacle. IP44
rated.

Circuit Breakers

2 pole 15 amp rated provides overload protection for
the 230VAC (European IEC-309) receptacle and the
230VAC duplex receptacle.

Single pole 15 amp rated provides overload protection
for the 115VAC (European IEC-309) receptacle.

Single pole 15 amp rated provides overload protection
for the 115VAC (5-20R) NEMA duplex receptacle.

GFCI (Ground Fault Circuit Interrupter):

• Protects both 115VAC auxiliary power receptacles.

• If the GFCI is tripped, see the Maintenence Section

for detailed information on testing and resetting the
GFCI.

The GFCI (Ground Fault Circuit Interrupter) electrical
receptacle is a device to protect against electric shock
should a piece of defective equipment connected to it
develop a ground fault. If this situation should occur,
the GFCI will trip, removing voltage from the output of
the receptacle. If the GFCI is tripped see the MAINTE-
NANCE section for detailed information on testing and
resetting it. The GFCI should be properly tested at
least once every month.

The 115V auxiliary power receptacles should only be
used with three wire grounded type plugs or approved
double insulated tools with two wire plugs. The current
rating of any plug used with the system must be at
least equal to the current capacity of the associated
receptacle.

RESIDUAL CURRENT DEVICE

The SAE-400® is configured to allow for the addition
of a Residual Current Device (RCD) to protect the
240V Single Phase Receptacle. The lower Control
Panel has a rectangular cut-out to accept a typical 2-
pole RCD along with a protective rubber boot. A cover
plate a label “RCD READY” covers the rectangular cut-
out, and secures a mounting bracket on the backside
of the panel.

Note: The (RCD) should be rated for at least 15 amps.

There are many suppliers of RCDʼs. One example is
Clipsal, part number 4RC225/30.

The protective boot can be obtained from:
APM-Hexseal, part number HE-1035.

See Section F Diagrams of this Operatorʼs Manual for
instructions on installing an RCD and protective rubber
boot.

GROUND STUD

Provides a connection point for connecting the
machine to earth ground. For the safest grounding pro-
cedure refer to “Machine Grounding” in the INSTALLA-
TION section of this manual.

SAE-400®