Nbox(b)tmne, g, h installation instructions, 4 installation - configuration, Check network – TREND NBOX(B)TMNE, G, H User Manual
Page 8: Connect local pc, Configure
8
NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 2, 07/01/2009
NBOX(B)TMNE, G, H
Installation Instructions
X
Q
T X -
T X +
R X - R X +
L A N A
NBOX(B)/TMN
O
I
NBOX(B)/TMN
?
NBOX(B)/TMN
?
T X -
T X +
R X - R X +
L A N A
Check Network
Not if local device connector
plugged into Dev A (1.4 step 9)
16
b
TX
(yellow)
a
RX
(yellow)
c
OK
(green)
TMN Faulty
Check network cabling
for short circuits with a
multimeter (NOT Megger)
Check baud rate
.
Power up other nodes until
faulty node is found (OK
). Correct fault.
Network Address Invalid
0,2,3 or >119
OK
OK
1.4 Installation - Configuration
(continued)
17
Connect Local PC
Cable /58-0750
25 Way D type Male
9 Way D type Female
If set up as in
1.4 step 9
WupDn or PowerTool
(not 962, 963, or 945)
18
Configure
e.g.
F
select deFault module
• Use WupDn or PowerTool.
• If on Lan or direct connected set Lan x, address =
switch setting.
• If on Internetwork set Lan = switch setting and
822 Toolbox, 921 only
(Direct connections see
1.4 steps 9 and 17).
or
Autodialling Manual,
90-1353
TMNE, G, H Data Sheet,
TA200734
to eXit module having
changed parameter
to Quit module and
discard changes
top Menu :
S t a t u s
R e c o r d
L i s t
D e l a y l i s t
d e F a u l t
H e l p
e X i t
Note that a PIN may be required to make changes in configuration mode. If the PIN has been forgotten the user should contact
Technical Support quoting the default generator number (Default Module) whereupon a default PIN will be supplied. This
will only work during the same configuration mode session i.e. the utility must not be exited between reading the generator
and entering the default PIN. After the PIN is entered a new PIN should be set up and remembered.
(for local configuration)
T M N
T M N