Install auto-dialled end, Test system – TREND NBOX(B)TMNE, G, H User Manual
Page 13
NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 2, 07/01/2009
13
Installation Instructions
NBOX(B)TMNE, G, H
1.4 Installation - Configuration
(continued)
T M N
I Q
T M N
Install auto-dialled end
28
Test System
29
Dialling messages are displayed by some supervisors and may help fault diagnosis.
DIALLING 01234123456
Dialling the number
UNOBTAINABLE WAIT xxmxxs
Modem has dialled and obtained busy signal or number unobtainable (must wait for delay to expire)
CONNECTED 01234123456
Connection achieved between IQ systems
DISCONNECTED 01234123456
Modem disconnected due to time out, or manual override
LINK-FAIL 01234123456
Failure of current link
REMOTE DISCONNECTION
Another device has requested priority use of far end modem
LOCAL DISCONNECTION
Another device has requested priority use of local modem
SECURITY FAIL
Auto-dial passwords do not match between TMNs.
In addition to normal network alarms the following alarms may be sent from the TMN to the TMN alarm destination node:
AONL
(Autodialler on line)
TMN powered up
BTNR
(No answer far site)
Lines engaged or telephone fault caused five failed attempts to connect.
Further dialling inhibited until re-dial delay expired (or general reset).
LINR
(No dial tone)
Modem fails to produce dial tone at start of call.
MONR (Local modem fault)
Modem failed to acknowledge request to dial.
PGNR (Pager bureau fault)
Pager failed to receive message although connection to pager bureau achieved.
TMN
Device
Device
A/D
Install
e.g.
Sensor values?
Alarms
Device
TMN
☎
a
Check telephone system
Check for dial and modem answer tones
b
Check communication
T M N
DTRA
(yellow)
TMN Busy to
Device A
Dev A connected
only
DTRB
(yellow)
TMN Busy to
MODEM
TMNE only
CTSA
(yellow)
Device A busy
Dev A connected
only
CTSB
(yellow)
MODEM Busy
to TMN
TMNE only
Modem communicating
MODEM
(yellow)
Modem not communicating
A/D may be:
MNC >=v2.54
AND
11
TMNH, TMNE TMNH, TMNE v4 TMNH, TMNE v4.4 915 + modem IQ2xx/ADL TMNG mobile phone When MNC dials into TMN it must have telephone number prefixed with SW. TMNE may not be able to communicate with MNC if its modem cannot achieve V21. TMN cannot dial into 915 + modem but 915 + modem can dial into TMN >= v4. TMN must be >= v4. a 2k4 bps enabled SIM and the IQ2xx/ADL must dial the To communicate with TMNG, adjust TMN v4.3 or greater Modem Link configuration setting 'Originate Msg Delay' to • Enter configuration mode (see 1.4 steps 9, 11, 12, 14, 17 MNC or TMNH, TMNE bureau or direct by TMNG. Mobile phone can only dial 11 TMNG can dial into AND v2.5, but AND v2.5 cannot dial into
To dial a TMNG, must use the TMNG's data number
To communicate with an IQ2xx/ADL a TMNG must have
TMNG's 2k4 bps data number
10 secs.
and 18 above).
• Type 'modem' at top configuration menu prompts.
• Type G3X to set 'oriGinate msg delay time' to 10s.
• Type X to exit configuration mode.
Mobile phone can be dialled from TMNE, TMNH by SMS
TMNG.
TMNG