Installation instructions nbox(b)tmne, g, h, 4 installation - configuration, Exit configuration – TREND NBOX(B)TMNE, G, H User Manual
Page 11: Configure gsm modem settings, Set up device (communicating by way of tmn), Devices
NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 2, 07/01/2009
11
Installation Instructions
NBOX(B)TMNE, G, H
• If 94x is using both TMNs/ANCs and XN28s then see Auto-dialling manual. If 94x is 945 1.01 or greater see
945 Engineering Manual.
• 962/963 can automatically seek next available autodialler (ANC, MNC, TMN, XN28) or can have particular
devices allocated to particular autodiallers (e.g. to ensure XN28s are used correctly).
• If dialling a TMNG, use its data number
• In 963, using TMNG, in Tcommsrv.ini set IdleTimeToDropline=100, and RemoteATDSites=60000 and ensure
[Grouping] has ‘TMN-G=G’.
• In PowerTool using TMNG in TrendCommsCodes.ini change mG=German Modem to ‘mG=TMN’, and add
‘cG=GSMIntegral’.
1
4
2
3
6
5
7
*
8
9
#
0
PHONE
94x/
962/963
modem
963
mobile phone
allows 963 to transmit
text messages (SMS)
to mobile phone, (no
need for TMN)
direct
SMS
modem
(
963 SMS
)
direct
Exit Configuration
23
X
" Exit from Utility"
1.4 Installation - Configuration
(continued)
Configure GSM modem settings
22
TMNG only
As a result of inserting the SIM card (1.4 step 10), select ‘init’ from top level config prompts
(see 1.4 step 18) to automatically re-initialize modem (v4.5 and greater only).
For TMNG v4.4 the settings must be entered manually:
• In configuration mode with the top menu prompts displayed, type 'direct'.
• Type “dAT+CNMI=2,1,1,0,0” to enable SMS received notification
• Type “dAT+CSMS=1” to set SMS commands to Phase 2+ version
• Type “dAT+ILRR=0” to disable data rate reports
• Type “dAT+CAOC=1” to disable charging information reports
• Type “dAT+CMGF=1” to set SMS message mode to text
• Type “dAT+CSMP=17,196,0,0” to set SMS validity period to 4 weeks
• Type “dAT+CSAS” to save the SMS settings
• Type “dAT&W” to save settings to modem stored profile
RS232
Set up device (communicating by way of TMN)
24
Devices:
TMN
TMN
Lan
I/N
IQ/822
WupDn
IQ/822
TMN
Device
TMN
• For autodialled or critical alarms target, set Outstation address as appropriate with Lan number set to zero if
TMN a local Lan, and set to destination Lan number if TMN on Internetwork. Put outstation address, Lan, and
phone number in TMN record.
• IC Comms - use with caution - see Auto-dialling manual
• WupDn doesn't inform if connected
• If dialling a TMNG, use its data number
direct
only old IQ or 822+/Toolbox -
see 1.4 steps 9 and 17
TMN
TMN
Lan
I/N
921
921
modem
direct
using SANC - no need for TMN.
• Use 921 auto-dialling mode. Use '==' method to put Lan number in auto-dial number table, and enter TMN address
- see 921 Manual.
• If dialling a TMNG, use its data number
TMN
TMN
Lan
I/N
921/
SET
921/
SET*
modem
direct
using SANC - no need for TMN.
• Use 921 auto-dialling mode. Either set autodialler address to 2 to find any available TMN (Lan or I/N), or set
autodialler address to specific TMN address.
• If 921 shares TMNs/ANCs and XN28s then they must be specifically addressed.
• If dialling a TMNG, use its data number
TMN
TMN
Lan
I/N
94x/
962/963
921 < v 2.5
IQ
822+/Toolbox
WupDn
RS232
RS232
921 => v 2.5
SET
94x Series/962/963
(+841, 842, 843, 845)
*SET v4
PowerTool