System Sensor MOD2W User Manual

Series loop test/maintenance module mod2w

background image

SS-560-000 1 I56-4001-000

i

3

Series Loop Test/Maintenance Module

MOD2W

*For use with 2-Wire i

3

series smoke detectors 2W-B, 2WT-B, and (one) 2WTR-B

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6583

www.systemsensor.com

SPECIFICATIONS
Electrical Specifications
Power Supply Voltage:

Resettable power; Min. 8.5 Volts DC (Power limited); Max. 35 Volts DC (Power limited);

Device Power-up Time:

200 milliseconds

Max. Standby Current:

60mA

Max. Alarm Current:

185mA

Nom. Standby Current:

38mA@12V, 20mA@24V

Alarm Contact Rating:

100 mA @ 36 Volts DC, resistive, 25 ohms

Maintenance Contact Rating:

100 mA @ 36 Volts DC, resistive, 25 ohms

Max. IDC Loop Wiring Resistance:

50 Ohms

Min. Reset Time:

300 milliseconds

Initial Communication Cycle:

6 minutes

EZ Walk Test Availability:

6 minutes after power up or panel reset

Physical Specifications
Operating Temperature Range:

0 - 50° C (32 - 122° F)

Operating Humidity Range:

5 - 95% RH

Storage Temperature Range:

-20 - 70° C (-4 - 158° F)

Height:

6.04 inches

Width:

6.04 inches

Depth:

1.16 inches

Shipping Weight:

0.6 lbs

Wire Gauge Acceptance:

Min: 22 AWG; Max: 14 AWG

2-wire Compatibility Requirements
Min. Loop Voltage:

12.6 Volts DC

Max. Loop Voltage:

14.52 Volts DC

Max. Loop Resistance:

50 Ohms

Max. Loop Ripple:

240 mVpp

Max. Loading Capacitance:

0.01 mF

Max. Alarm Current:

43.5 mA

Max. Reset Voltage:

0.30 Volts DC

Alarm Delay:

n/a

Min. Alarm Reset Time:

0.3 seconds

Max. Normal Load Current:

1.2 mA

Zone Type:

Standard

EOL Device:

3.9k Ohms (+-5%)

Loop Style:

B and D

Compatibility Zone Identifier:

A

Detector Zone Identifier:

A

Max. Detectors Per Zone:

(12) 2-wire i

3

series model #2W-B, 2WT-B, (one) 2WTR-B

I56-400

1-000

BEFORE INSTALLATION
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
module will be installed in an existing operational system, inform the operator
and local authority that the system will be temporarily out of service. Discon-
nect power to the control panel before installing the module.

Notice: This manual should be left with the owner/user of this equipment.
This product is intended for use in ordinary indoor locations.
GENERAL DESCRIPTION
The MOD2W allows a control panel to receive a “need for maintenance” sig-
nal from two–wire i

3

series smoke detectors, model numbers 2W–B, 2WT–B

and one 2WTR-B. The module uses a form C zone relay to initiate “out of sen-
sitivity” and “freeze trouble”, a form A zone alarm relay and a second form
A zone relay to indicate loop fault. An EZ Walk Test puts all detectors on the
loop into a Walk Test mode for easy verification of detector loop wiring. The
module allows 2-wire smoke detectors to be used on any compatible 4-wire
control panel and provides Style D wiring on the detector loop.
VISIBLE ANNUNCIATON
The MOD2W has three visible LED’s: The green LED is a supervisory LED; it
blinks during power on, reset, and during normal operation. The yellow LED

is used to indicate a loop wiring fault and will blink when it is in EZ Walk test
mode. The red LED signals smoke events; it blinks during smoke maintenance
events and lights constantly during smoke alarm events.
FIGURE 1: MODULE FRONT VIEW

Green LED

Yellow LED

Red LED

EZ Walk Test Switch

S0331-02