System Sensor MOD2W User Manual
Series loop test/maintenance module mod2w
SS-560-000 1 I56-4001-000
i
3
Series Loop Test/Maintenance Module
MOD2W
*For use with 2-Wire i
3
series smoke detectors 2W-B, 2WT-B, and (one) 2WTR-B
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6583
www.systemsensor.com
SPECIFICATIONS
Electrical Specifications
Power Supply Voltage:
Resettable power; Min. 8.5 Volts DC (Power limited); Max. 35 Volts DC (Power limited);
Device Power-up Time:
200 milliseconds
Max. Standby Current:
60mA
Max. Alarm Current:
185mA
Nom. Standby Current:
38mA@12V, 20mA@24V
Alarm Contact Rating:
100 mA @ 36 Volts DC, resistive, 25 ohms
Maintenance Contact Rating:
100 mA @ 36 Volts DC, resistive, 25 ohms
Max. IDC Loop Wiring Resistance:
50 Ohms
Min. Reset Time:
300 milliseconds
Initial Communication Cycle:
6 minutes
EZ Walk Test Availability:
6 minutes after power up or panel reset
Physical Specifications
Operating Temperature Range:
0 - 50° C (32 - 122° F)
Operating Humidity Range:
5 - 95% RH
Storage Temperature Range:
-20 - 70° C (-4 - 158° F)
Height:
6.04 inches
Width:
6.04 inches
Depth:
1.16 inches
Shipping Weight:
0.6 lbs
Wire Gauge Acceptance:
Min: 22 AWG; Max: 14 AWG
2-wire Compatibility Requirements
Min. Loop Voltage:
12.6 Volts DC
Max. Loop Voltage:
14.52 Volts DC
Max. Loop Resistance:
50 Ohms
Max. Loop Ripple:
240 mVpp
Max. Loading Capacitance:
0.01 mF
Max. Alarm Current:
43.5 mA
Max. Reset Voltage:
0.30 Volts DC
Alarm Delay:
n/a
Min. Alarm Reset Time:
0.3 seconds
Max. Normal Load Current:
1.2 mA
Zone Type:
Standard
EOL Device:
3.9k Ohms (+-5%)
Loop Style:
B and D
Compatibility Zone Identifier:
A
Detector Zone Identifier:
A
Max. Detectors Per Zone:
(12) 2-wire i
3
series model #2W-B, 2WT-B, (one) 2WTR-B
I56-400
1-000
BEFORE INSTALLATION
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
module will be installed in an existing operational system, inform the operator
and local authority that the system will be temporarily out of service. Discon-
nect power to the control panel before installing the module.
Notice: This manual should be left with the owner/user of this equipment.
This product is intended for use in ordinary indoor locations.
GENERAL DESCRIPTION
The MOD2W allows a control panel to receive a “need for maintenance” sig-
nal from two–wire i
3
series smoke detectors, model numbers 2W–B, 2WT–B
and one 2WTR-B. The module uses a form C zone relay to initiate “out of sen-
sitivity” and “freeze trouble”, a form A zone alarm relay and a second form
A zone relay to indicate loop fault. An EZ Walk Test puts all detectors on the
loop into a Walk Test mode for easy verification of detector loop wiring. The
module allows 2-wire smoke detectors to be used on any compatible 4-wire
control panel and provides Style D wiring on the detector loop.
VISIBLE ANNUNCIATON
The MOD2W has three visible LED’s: The green LED is a supervisory LED; it
blinks during power on, reset, and during normal operation. The yellow LED
is used to indicate a loop wiring fault and will blink when it is in EZ Walk test
mode. The red LED signals smoke events; it blinks during smoke maintenance
events and lights constantly during smoke alarm events.
FIGURE 1: MODULE FRONT VIEW
Green LED
Yellow LED
Red LED
EZ Walk Test Switch
S0331-02