System Sensor D4120, D4P120, and D4S User Manual
Page 8

THREE-YEAR LIMITED W
ARRANTY
Sy
stem Sensor w
arr
ants its enclosed pr
oduct to be fr
ee fr
om defects in materials and
w
orkmanship under normal use and service for a period of thr
ee y
ear
s fr
om date of
manufactur
e. S
ystem Sensor mak
es no other e
xpr
ess w
arr
anty for the enclosed pr
oduct.
No agent, r
epr
esentativ
e, dealer
, or emplo
yee of the Compan
y has the authority to in
-
cr
ease or alter the obligations or limitations of this W
arr
anty
. The Compan
y’
s obligation
of this W
arr
anty shall be limited to the r
eplacement of an
y part of the pr
oduct which
is found to be defectiv
e in materials or w
orkmanship under normal use and service
during the thr
ee y
ear period commencing with the date of manufactur
e. After phoning
Sy
stem Sensor’
s toll fr
ee number 800-SENSOR2 (736-7672) for a R
eturn A
uthorization
number
, send defectiv
e units postage pr
epaid to: S
ystem Sensor
, R
eturns Department, RA
#__________,
3825
Ohio
A
venue
,
St.
Charles
,
IL
60
174.
Please
include
a
note
describing
the malfunction and suspected cause of failur
e. The Compan
y shall not be obligated to
replace units which ar
e found to be
defectiv
e because
of damage
, unr
easonable use
,
modifications
, or alter
ations occurring after the date of manufactur
e. In no case shall the
Compan
y be liable for an
y consequential or incidental damages for br
each of this or an
y
other W
arr
anty
, e
xpr
essed or implied whatsoe
ver
, e
ven if the loss or damage is caused b
y
the Compan
y’
s negligence or fault. Some states do not allo
w the e
xclusion or limitation of
incidental or consequential damages
, so the abo
ve limitation or e
xclusion ma
y not apply
to y
ou. This W
arr
anty giv
es y
ou specific legal rights
, and y
ou ma
y also ha
ve other rights
which v
ary fr
om state to state
.
Please r
efer to inser
t for the Limitations of Fir
e Alar
m Systems
Sensor
D4S
Power Board
D4P120
At power-up or reset at the panel, th
e
sensor will take approx 35 seconds
to initialize.
Also occurs if the sensor
has been removed and restored in
the base in the sensor housing.
RED Blink every 5
seconds
Alternatin
g
Green/amber
every 1 second
Supervisory rela
y:
Te
rminals 3 and 14 are closed.
Alarm Rela
y:
Te
rminals 4 and 5 are open.
Aux Relay
does not switch states:T
erminals 6 and 16 are closed,
Te
rminals 8 and 18 are closed
Sensor is missing during the seven
minute tamper Delay
, if selected.
Of
f
Alternatin
g
Green/amber
every 1 second
Supervisory rela
y:
Te
rminals 3 and 14 are closed
Alarm Relay
: Te
rminals 4 and 5 are open.
Aux Rela
y does not switch states:T
erminals 6 and 16 are closed,
Te
rminals 8 and 18 are closed
Maintenance
Sensor D4S is outside it's UL
approved sensitivity limits and needs
to be cleaned or replaced.
RED Blink every 5
seconds
Amber Blink
every 5 seconds
Supervisory rela
y:
Te
rminals 3 and 14 are closed.
Alarm Rela
y:
Te
rminals 4 and 5 are open.
Aux Rela
y does not switch states:T
erminals 6 and 16 are closed,
Te
rminals 8 and 18 are closed
.Unit loses Power
Of
fO
ff
.Cover
Tamper Delay times out
Green Blink every 5
seconds
Amber solid
.Wiring Problems between the
Sensor and the Power Boar
d
Of
fA
mber solid
.Mismatch between the number of
sensors connected and the Dip
Switch setting
1 sensor connected,2 selected
Green blink every 5
seconds on first
senso
r.
No second senso
r.
LED1 Green
blink every 5
seconds
LED2
Amber
solid
2 sensors connected,1 selected
Green blink every 5
seconds on first
senso
r.
LED's of
f on second
sensor
LED1 Green
blink every 5
seconds
LED2
Amber
solid
Alarm
Unit detects smok
eS
olid Re
dS
olid Red
Supervisory rela
y:
Te
rminals 3 and 14 are closed
Alarm Relay
: Te
rminals 4 and 5 are closed.
Aux Rela
y switches states:
Te
rminals 6 and 16 are open,
Te
rminals 8 and 18 are open
Standby
Unit has Power and it is not in
initialization,
Tr
ouble, Maintenance or
Alarm.
Green Blink every 5
seconds
Green Blink
every 5 seconds
Supervisory rela
y:
Te
rminals 3 and 14 are closed
Alarm Rela
y:
Te
rminals 4 and 5 are open.
Aux Relay
does not switch states:
Te
rminals 6 and 16 are closed,
Te
rminals 8 and 18 are closed
LED Status
Status
Descriptio
n
Status of Relays
Supervisory rela
y:
Te
rminals 3 and 14 are open.
Alarm Relay:
Te
rminals 4 and 5 are open.
Aux Relay
does not switch states with no shutdown on
Tr
ouble selected:
Te
rminals 6 and 16 are closed.
Te
rminals 8 and 18 are closed.
Aux Rela
y Switches states with shutdown on
Tr
ouble selected:
Te
rminals 6 and 16 are open,
Te
rminals 8 and 18 are open
Trouble
Sensor
Initialization
TABLE 3. DETECTOR ST
ATUS INDICA
TION
NO
TE: Ther
e ar
e tw
o LED’
s on the P
ow
er boar
d D4P12
0, each indicating the Status of the tw
o sensor
s connected.
When ther
e is only one sensor connected, LED2 will r
emain off.
NO
TE: If an
y other visual indication is noted contact S
ystem Sensor technical support at 1-800-SENSOR2.
SS-300-000
8 I56-2967-006R