System Sensor RTS151 User Manual
Page 2

D440-01-00 2 I56-0469-014
©2011 System Sensor
three-Year limited Warranty
System Sensor warrants its enclosed product to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for the enclosed product.
No agent, representative, dealer, or employee of the Company has the authority to in-
crease or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the replacement of any part of the product which
is found to be defective in materials or workmanship under normal use and service
during the three year period commencing with the date of manufacture. After phoning
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Returns Department, RA
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing
the malfunction and suspected cause of failure. The Company shall not be obligated to
replace units which are found to be defective because of damage, unreasonable use,
modifications, or alterations occurring after the date of manufacture. In no case shall the
Company be liable for any consequential or incidental damages for breach of this or any
other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by
the Company’s negligence or fault. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation or exclusion may not apply
to you. This Warranty gives you specific legal rights, and you may also have other rights
which vary from state to state.
fIGure 5. WIrInG DIaGram for rtS151 to DH100aCDC 4-WIre
DuCt Smoke DeteCtor:
fIGure 6. WIrInG DIaGram for rtS151 to DH100 2-WIre DuCt
Smoke DeteCtor:
15
20
2
11
2
1
Alarm Signal +
Aux. Power –
Reset
Test
(Red LED) Alarm
DH100ACDC
RTS151
5
4
3 Reset
Test
Field
Installed
Jumper
1
2
3
4
5
6
3
4
5
Test +
Test / Reset –
Reset +
Test
Reset
RA +
RA –
V Out +
DH100
RTS151
6
2
1 Alarm
LED
No Connection
H0198-04
H0612-11
H0197-01
fIGure 7. WIrInG DIaGram for rtS151 to DH400aCDC DuCt
Smoke DeteCtor:
ALARM SIGNAL (+)
AUX POWER (–)
5
6
1
2
R
E
D
5
3
4
3 RESET
TEST
4
FIELD
INSTALLED
JUMPER
RESET (–)
TEST (–)
DH400ACDC
RTS151
H0149-02
fIGure 8. WIrInG DIaGram for rtS151 to Beam1224/
Beam1224S Smoke DeteCtor:
1
2
3
4
5
3
2
1
5
4
RTS151
BEAM1224/BEAM1224S
REMOTE ALARM OUT
AUX (–)
TEST INPUT
REMOTE TROUBLE OUTPUT
RESET INPUT
TEST
RESET
T2-3
T3-3
T2-4
T2-2
T2-1
OPTIONAL YELLOW LED
(RED LED) ALARM
H0586-03
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
RTS151
(OPTIONAL) REMOTE
TEST STATION
MAGNET
TEST
SWITCH
ALARM
LED (RED)
4
5
2
1
(+)
(–)
+ RA
+ RTS
– RA
+ TEST COIL
– TEST COIL
+ IN
+ OUT
–
(–)
(+)
D2
24 VDC
AUX POWER
SUPPLIED
BY USER
(100mA
SUPPLY)
RTS151
(OPTIONAL) REMOTE
TEST STATION
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
MAGNET
TEST
SWITCH
ALARM
LED (RED)
4
5
2
1
(+)
(–)
+ RA
+ RTS
– RA
+ TEST COIL
– TEST COIL
+ IN
+ OUT
–
24 VDC
AUX POWER
SUPPLIED
BY USER
(100mA
SUPPLY)
D2
NOTE: THE USE OF THE RTS151 REQUIRES THE INSTALLATION OF
AN ACCESSORY COIL, DCOIL, SOLD SEPARATELY.
METHOD #1 - AUX POWER LOCATED
AT DUCT DETECTOR
METHOD #2 - AUX POWER LOCATED
AT TEST STATION
fIGure 4. WIrInG DIaGram for rtS151 to D2-2WIre DuCt Smoke DeteCtor: