Troubleshooting

SPEEDMASTER™ OPERATION MANUAL

Symptom

Possible

Causes

Suggested

Solutions

Fuse blows or circuit
breaker trips

Line fuse does not
blow or circuit
breaker does not
trip, but the motor
does not run

1. Line fuses or circuit

breakers are the
wrong size.

2. Motor cable or

armature is shorted to
ground.

3. Nuisance tripping

caused by a
combination of
ambient conditions
and high-current
spikes.

1. Reference signal or

speed adjust pot is set
to zero speed.

2. Reference signal or

speed adjust
potentiometer
connections are open.

1. Check that line fuses

or circuit breakers
are the proper size.

2. Check motor cable

and armature for
shorts.

3. Add a blower to cool

the drive
components;
decrease TORQUE
settings, or resize
motor and drive for
actual load demand,
or check for
incorrectly aligned
mechanical
components or
“jams”. See page 14
for information on
adjusting the
TORQUE trimpot.

1. Increase reference

signal or speed
adjust potentiometer
setting.

2. Check that the

reference signal or
speed adjust
potentiometer
connections are not
open.