D. programming the system setting, E. system setting program navigation – HTP PHE199-119 User Manual
Page 55
![background image](/manuals/350214/55/background.png)
55
LP-314 REV. 3.24.14
CLOCK YEAR
08/28/2009 Fr 10:01A
Function: Adjusts the year setting.
CLOCK MONTH
08/28/2009 Fr 10:01A
Function: Adjusts the month setting.
CLOCK DATE
08/28/2009 Fr 10:01A
The clock is set.
Table 14
– Clock Settings
NOTE: The clock does not automatically adjust for Daylight Savings Time, and requires manual adjustment.
D. PROGRAMMING THE SYSTEM SETTING
NOTE: Programming the control is not possible when the unit is firing. Make sure any input (such as the thermostat) is turned off, so the
boiler will remain idle to allow programming.
SCREEN
DESCRIPTION
ENTER MENU CODE
000
To access the system setting program, press and hold the ENTER Key for 4 seconds, until the display shows the
screen at left.
ENTER MENU CODE
925
Using the arrow keys on the display, log in your
System Menu Access Code “925”. To confirm code, press ENTER
to access system setting program navigation menu.
Table 15
– System Settings
E. SYSTEM SETTING PROGRAM NAVIGATION
Once the System Menu Access Code is confirmed, the user can start to set the System Parameters Menu. Use the arrow keys on the
display to navigate through the different program settings. To change an appliance setting, press ENTER. Increase system settings by
pressing
▲ and decrease by pressing ▼ on the display.
Listed below are the system settings that can be programmed into the control.
SCREEN
DESCRIPTION
Function 1
Factory Program Mode
MODE 1
PHOENIX
This screen indicates that the control is configured correctly. Do not change this setting.
Function 2
Max Tank Temp
MAX TANK TEMP 2
180
o
F
Sets the overall tank temperature maximum limit. Factory default 180
o
F (Range 95
o
F to 185
o
F).
Function 3
DHW Offset Temp
OFFSET 3
0
o
F
Not Used.
Function 4
Warm Weather Shutoff
WARM WEATHER OFF 4
68
o
F
Warm Weather Shutoff disables the heating module and the Total System Control will then optimize for domestic hot
water only. Warm Weather Shutoff will occur if the programmed outdoor temperature is exceeded by the current
outdoor sensor temperature. Factory default 68
o
F (Range 41
o
F to 122
o
F).
Function 5
Min Outdoor Temp
MIN OUTDOOR TEMP 5
5
o
F
Allows the user to set the minimum outdoor design temperature for the system. Factory default 5
o
F (Range -49
o
F to
122
o
F).
Function 6
Max Supply Temp
MAX SUPPLY TEMP 6
140
o
F
Allows the user to set the maximum design supply temperature based on the minimum outdoor design temperature.
Factory default 140
o
F (Range 77
o
F to 170
o
F).
Function 7
Max Outdoor Temp
MAX OUTDOOR TEMP 7
68
o
F
Allows the user to set the maximum outdoor design temperature for the system. Factory default 68
o
F (Range 32
o
F to
95
o
F).
Function 8
Min Supply Temp
MIN SUPPLY TEMP 8
120
o
F
Allows the user to set the design supply water temperature based on the maximum outdoor design temperature.
Factory default 120
o
F (Range 32
o
F to 200
o
F).
Function 9
Min Tank Temp
MIN TANK TEMP 9
68
o
F
Allows the user to set the minimum tank temperature. Factory default 68
o
F (Range 32
o
F to 200
o
F).
Function 10
CH Post Pump Time
CH POST PUMP TIME 10
0 MINUTES
Allows the user to set the central heating pump post purge time once the thermostat is satisfied. Factory default 0
minutes (Range 0 to 10
minutes).