HTP PHE199-119 User Manual
Page 52
![background image](/manuals/350214/52/background.png)
52
LP-314 REV. 3.24.14
Figure 29
10. Press and hold ENTER for 4 seconds until you see the screen to log in the access code.
11. Use the and arrow keys to move the blinking zero to the left and right. Next,
use the
▲ and ▼ arrow keys on to log in the access code of 925. Press ENTER to
access the System Setting Program Navigation menu. Once the code is confirmed,
you can set the System Settings. Use and to navigate through the System Setting Program.
12. Press 3 times to scroll to Function 4 -
“WARM WEATHER OFF”. This is the warm weather shutdown. This function determines
the outdoor temperature that will turn off the hydronic heating module and operate the appliance only as an appliance for the warmer
weather. To adjust this value, press ENTER and the factory default of 68°F starts to blink. Use
▲ and ▼ to adjust this value to your
system needs. To store the new value press ENTER.
13. Next, press once to scroll to Function 5 -
“MIN OUTDOOR TEMP”. This function is the first step to setting the outdoor reset
curve. Enter
your system’s minimum outdoor temperature value. To adjust the value, press ENTER and the factory default of 5 °F starts
to blink. Use
▲ and ▼ to adjust to your designed temperature. To store the new value press ENTER.
14. Press once to scroll to Function 6 -
“MAX SUPPLY TEMP”. This function is the second step to setting your outdoor reset curve.
Enter
your system’s hydronic heating module maximum supply temperature value. To adjust the value, press ENTER and the factory
default of 140 °F will start to blink. Use
▲ and ▼ to adjust to your designed temperature. To store the new value press ENTER. NOTE:
This should be the same value entered in step 5.