E. how to verify combustion, Part 9 - start-up procedure, A. fill and purge dhw – HTP PHE199-119 User Manual
Page 49

49
LP-314 REV. 3.24.14
Do not do a gas conversion on this unit without an officially approved conversion kit and instructions supplied by HTP. Failure to do so
could result in serious injury or death.
E. HOW TO VERIFY COMBUSTION
To activate service mode, press the up arrow
▲ and ENTER key together for 1 second.
The unit will go through the ignition sequence. Press
▲ to increase, or ▼ to decrease
fan speed.
To leave service mode, press ▲ and ▼ simultaneously.
COMBUSTION SETTINGS ON ALL MODELS
Natural Gas
Propane LP
Fan Speed
Low
Ignition
High
Low
Ignition
High
Carbon Monoxide PPM
1
– 10
2 - 15
2
– 20
1
– 10
2 - 15
2
– 20
Carbon Dioxide (CO
2
)
8 - 10%
8
– 10%
8 - 10%
8 ½ - 10 ½%
8 ½ - 10 ½%
9 - 11%
Table 10
FAN SPEEDS
BTU
IGNITION
MIN
MAX
130,000
3000
2000
7300
199,000
3000
2000
9100
Table 11
PART 9 - START-UP PROCEDURE
FOR YOUR OWN SAFETY READ BEFORE OPERATING
1. This boiler does not have pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the
burner by hand.
2. BEFORE OPERATING: smell all around the boiler area for gas. Be sure to smell next to the floor because some gas is heavier than
air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any boiler.
Do not touch any electric switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas suppliers' instructions.
If you cannot reach your gas supplier, call the fire department.
Turn off gas shutoff valve (located outside of the boiler) so that the handle is crosswise to the gas pipe. If the handle will not
turn by hand, don't try to force or repair it, call a qualified service technician. Force or attempted repair may result in a fire or
explosion.
4. Do not use this boiler if any part has been under water. Immediately call a qualified service technician to inspect the boiler and to
replace any part of the control system and any gas control that has been damaged.
5. The boiler shall be installed so the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during
boiler operation and service (circulator replacement, condensate trap, control replacement, etc.)
Failure to follow these instructions could result in property damage, serious personal injury, or death.
A. FILL AND PURGE DHW
Ensure the appliance is full of water before firing the burner. Failure to do so will damage the appliance. Such damage IS NOT covered
by warranty, and could result in property damage, serious personal injury, or death.