Securitron AQU128B User Manual
Page 6
Page 6
P/N 500-30045
Rev. A, 04/13
2. Connecting the Battery
Plug battery cable assembly into battery backup plug -BAT+.
Install batteries. Mark batteries with “Installed” date and “Replace By” date according to manufacturer’s
battery life recommendations.
Connect leads to batteries.
For 12VDC operation:
Connect red battery lead to the Positive (+) battery terminal.
Connect black battery lead to the Negative (-) battery terminal.
D
.
Testing
1.
Test Input and Outputs
AC Input: Enable AC power to input line. Confirm LED on front of enclosure is lit.
DC output: If connected to load or distribution board, DC output indicator on power module will be lit.
If not connected to load or distribution board, test output with Amp Meter to verify current.
AC Fail Notification: Disable AC power to input line. If AC fail notification is configured, the switch will
change state, triggering the notification output.
Low Battery Notification: Disable AC power to input and allow batteries to run down to Low Battery
Warning.
Recommended Annual Maintenance
Battery Test
Turn off AC power
Check DC output voltage under battery operation.
For fully charged batteries, voltage should be above 11.5V. If voltage is below this range, test batteries
per battery manufacturer instructions and replace if needed.
AC Fail Test
Turn off AC power. TROUBLE switch should trigger an alert upon disconnect or upon fail over to
battery power.
Problems with installation? Call Securitron: 1-800-MAG-LOCK