5. Make DC Power Output Connections to Devices
Using 10AWG to 24 AWG wire, connect the device wire run to the
DC outputs. Maintain separation from battery cable placement by
passing wires under power module before connecting to terminal
screws.
Connect the Positive wire to DC OUT Positive (+) terminal.
Connect the Negative wire to DC OUT Negative (-) terminal.
NOTE: Use appropriate wire gauge for the Amperage and
distance of the run. For more info, see Wire Loss Calculator
at http://www.securitypower.com/AN2Wire.html
6. Wiring for Status Monitoring Options
The diagram shows basic wiring to provide output to a control panel or local alarm
for notification of over-voltage or under-voltage.
AC-ON state energized the NO/C switch.
The Switch changes state when voltage exceeds 28.2 VDC or falls below 24.2 VDC
including for low battery power.
8. Turn on AC Power
After making electric connections, turn on AC power before installing batteries. The AC LED power indicator
should be lit.
Negative
+/Positive
-/Negative
NO
C NC
Trouble
Access Control
System Panel