7 PRGM/RUN SWITCH

Use the PRGM/RUN switch on the X11CA-IM to set the mode to either program
mode or run mode.

7.1 Program Mode

In the program mode, you can configure or change the configuration of the alarm
modules with the Configuration software running on the host computer.

To set X11CA-IM to program mode, set the switch to PRGM and make sure that
the cable is connected from the Modbus communication port (P2) on the X11CA-
IM to the serial port of the host computer. Verify that the RUN and ERROR LEDs
flash simultaneously.

Refer to X11CA Configuration Software User’s Manual (Doc # :X11CA-3001-
IOM
) for detail.

7.2 Run Mode

In the run mode, the X11CA-IM scans all the activities of the alarm modules and
activates the relay outputs and its push button functions.

7.2.1 Relay Outputs

There are five Relays on the X11-CA-IM as follows:

? RUN Relay indicates the power on condition and is normally energized
? REFLASH Relay is not used in this revision of the firmware.
? CTA Relay is a Common Trouble Alarm and will be energized if one or more

than one input in any Alarm card is on.

? Relay A1 is HORN1 relay and will be energized according to the sequence

programmed in the ALARM card.

? Relay A2 is HORN2 relay and will be energized according to the sequence

programmed in the ALARM card.

7.2.2 Functions of the Push Buttons