Safety ground, Input voltage selection, Interlocks – Ransburg 9060 LV Cascade Controller 80131-XXX User Manual
Page 22: 9060 cascade low voltage controller - installation
9060 Cascade Low Voltage Controller - Installation
17
CP-13-07.2
SAFETY GROUND
Crimp the appropriate connector onto the
ground wire assembly and install from the
Controller ground stud, located on the side
panel, to a true earth ground.
The ground wire assembly MUST be
connected from the Controller ground
stud to a true earth ground.
!
C A U T I O N
INPUT VOLTAGE
SELECTION
The 9060 Controller accepts universal input
voltage between 100 and 240 VAC at 50 or 60
Hz. There is no need to change any switch
settings when changing input from 110 to 240
VAC or from 240 to 110 VAC.
INTERLOCKS
Interlocks required by code are as follows:
•
Booth Fan Interlock - When the booth fan is
on, a contact closure is made.
•
Conveyor Interlock - When the conveyor is
moving, a contact closure is made.
•
Solvent Interlock - When solvent supply to
the applicator is off, a contact closure is
made.
Failure to connect interlocks could re-
sult in a fire or explosion.
!
W A R N I N G
ALWAYS ensure that high voltage is
OFF before flushing the spray applicator
with solvent. NEVER flush the spray ap-
plicator with high voltage ON, as this is a
severe fire hazard and risk to personnel
safety. It is recommended that the high
voltage control be interlocked with the sol-
vent flush signal so that high voltage is
automatically locked out whenever flush-
ing occurs. Consult your authorized
Ransburg representative for information
on interlocking the high voltage OFF sig-
nal with the solvent flush signal.
!
W A R N I N G
As outlined in NFPA-33, OSHA, and EN 50176,
the AC power line must be series interlocked
with both the exhaust fan and conveyor.
To install the Controller interlocks perform the
following:
1.
Turn the 9060 Controller off, disconnect
it from its AC source, and remove the
fuses.
ALWAYS double check that the Con-
troller is unplugged from its AC outlet
before working with any internal wiring.
!
W A R N I N G
3. Using a small blade screwdriver, remove
the factory installed test jumper from 1TB-
L2 to 1TB-L3.
4.
Using a shielded cable for the interlock
wiring (supplied by user), route through the
interlock connector on the side of the 9060
Controller and terminate 1TB-L2 and 1TB-
L3 as shown in Figure 11. The shielded
cable must have a minimum rating of 300V
All 9060 units (80131-XXX) shipped
from the factory for either 110 VAC input
or 240 VAC input will have a 72771-06, 1
Amp front panel fuses installed.
N O T E