System specifications, System capacity, Electrical specifications – FIREPOWER MS-10UD-7 User Manual

Page 4: Cabinet specifications, Shipping specifications, Temperature and humidity ranges, Agency listings and approvals, Nfpa standards

background image

Page 4 of 4 — DF-52416:C • 05/12/2009

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.

www.firelite.com

Made in the U.S. A.

System Capacity

Annunciators ...................................................................... 8

Electrical Specifications

MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ,
1.0 A

MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ,
3.90 A

MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ,
2.20 A.

Wire size: minimum 14 AWG (2.0 mm

2

) with 600 V insula-

tion, supervised, nonpower-limited

Cabinet Specifications

Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x
0.72" (1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x
16.65" (42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring
(TR-CE):
22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide.

Shipping Specifications

Dimensions:

20.00" (50.80 cm.) high

22.5" (57.15 cm.) wide

8.5" (21.59 cm.) deep.

Weight: 27 lb (12.20 kg)

Temperature and Humidity Ranges

This system meets NFPA requirements for operation at 0 –
49°C/32 – 120°F and at a relative humidity 93% ± 2% RH
(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the
useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme tempera-
ture ranges and humidity. Therefore, it is recommended that
this system and its peripherals be installed in an environment
with a normal room temperature of 15 – 27°C/60 – 80°F.

Agency Listings and Approvals

The listings and approvals below apply to the basic MS-5UD-3
and MS-10UD-7 control panels. In some cases, certain mod-
ules or applications may not be listed by certain approval
agencies, or listing may be in process. Consult factory for lat-
est listing status.

UL Listed: File S624

• FM Approved

CSFM: 7165-0075:214

MEA: MEA: 333-07-E

NOTE: For ULC-listed models, see df-60440.

NFPA Standards

The MS-5UD/MS-10UD(E) Series complies with the following
NFPA 72 Fire Alarm Systems requirements:

– LOCAL (Automatic, Manual, Waterflow and Sprinkler

Supervisory).

– AUXILIARY (Automatic, Manual and Waterflow) (requires

4XTMF).

– REMOTE STATION (Automatic, Manual and Waterflow)

(Where a DACT is not accepted, the alarm, trouble and
supervisory relays may be connected to UL 864 listed
transmitters. For reverse polarity signaling of alarm and
trouble, 4XTMF is required.)

– PROPRIETARY (Automatic, Manual and Waterflow).

– CENTRAL STATION (Automatic, Manual and Waterflow,

and Sprinkler Supervised).

– OT, PSDN (Other Technologies, Packet-switched Data

Network)

FireLite® Alarms and System Sensor® are registered trademarks of
Honeywell International Inc.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

SYSTEM SPECIFICATIONS

This manual is related to the following products: