DF-52416:C • 05/12/2009 — Page 3 of 4

Initiating Device Circuits – TB4 (and TB 6 on MS-10UD-7
only):

Alarm Zones 1 - 5 on TB 4 (MS-5UD-3 and MS-10UD-7).

Alarm Zones 6 - 10 on TB6 (MS-10UD-7 only).

Supervised and power-limited circuitry.

Operation: All zones Style B (Class B).

Normal Operating Voltage: Nominal 20 VDC.

Alarm Current: 15 mA minimum.

Short Circuit Current: 40 mA max.

Maximum Loop Resistance: 100 ohms.

End-of-Line Resistor: 4.7K ohm, 1/2 watt (P/N 71252 UL-
listed).

Standby Current: 2 mA.

Refer to the Fire•Lite Device Compatibility Document for listed
compatible devices.

Notification Appliance Circuits – TB5 (and TB 7 on MS-
10UD-7 only):

Four NACs

Operation: Style Y (Class B)

Special Application power

Supervised and power-limited circuitry

Normal Operating Voltage: Nominal 24 VDC

Maximum Signaling Current: 3.0 A for MS-5UD-3, 2.5 A
maximum per NAC; 7.0 A for MS-10UD-7(E), 3.0 A maxi-
mum per NAC.

End-of-Line Resistor: 4.7K ohm, 1/2 watt (Part #71252)

Max. Wiring Voltage Drop: 2 VDC

Refer to the Fire•Lite Device Compatibility Document for com-
patible listed devices.

Form C Relays – TB8:

Relay 1 (factory default programmed as Alarm Relay)

Relay 2 (factory default programmed as fail-safe Trouble
Relay)

Relay 3 (factory default programmed as Supervisory Relay)

Special Application Resettable Power – TB9:

Jumper selectable by JP31 for resettable or nonresettable
power.

Operating voltage: 24 VDC nominal.

Maximum available current: 500 mA - appropriate for pow-
ering four-wire smoke detectors.

Power-limited circuit.

Refer to the Fire•Lite Device Compatibility Document for listed
compatible devices.

Remote Sync Output - TB2: Remote power supply synchro-
nization output, only required for the MS-5UD-3. 24 VDC nom-
inal special application power. Maximum current is 40 mA.
End-of-Line Resistor: 4.7K ohm. Supervised and power-lim-
ited circuit.

Product Line Information

MS-5UD-3: Five-zone, 24-volt Fire Alarm Control Panel
(includes backbox, FLPS-3 power supply, technical manual,
and a frame & post operating instruction sheet).

MS-10UD-7: Ten-zone, 24-volt Fire Alarm Control Panel
(includes backbox, FLPS-7 power supply, technical manual,
and a frame & post operating instruction sheet).

MS-10UD-7E: Same as above with 240 VAC FLPS-7.

IPDACT, IPDACT-2/2UD Internet Monitoring Module:
Mounts in bottom of enclosure with optional mounting kit (PN
IPBRKT). Connects to primary and secondary DACT tele-

phone output ports for internet communications over customer
provided ethernet internet connection. Requires compatible
Teldat Visoralarm Central Station Receiver. Can use DHCP or
static IP. (See data sheet df-52424 for more information.)

IPBRKT: Mounting kit for IPDACT in common enclosure.

IPSPLT: Y Adaptor option to allow connection of both panel
dialer outputs to one cable input to IPDACT (sold separately).

OPTIONAL MODULES

CAC-5X: Optional (Class A) Converter Module. Converts Style
B (Class B) Initiating Device Circuits to Style D (Class A); and
Style Y (Class B) Notification Appliance Circuits to Style Z
(Class A). Connects to J2 on the MS-5UD-3 and MS-10UD-
7(E) main circuit board and to J7 on the MS-10UD-7(E).

NOTE: Two Class A Converter Modules are required for the ten-
zone panel.

4XTMF: Transmitter module. Provides a supervised output for
local energy municipal box transmitter and alarm and trouble
reverse polarity. Includes a disable switch and disable trouble
LED. A module jumper option allows the reverse polarity circuit
to open with a system trouble condition if no alarm conditions
exists. Mounts to the main circuit board connectors J4 and J5.

COMPATIBLE ANNUNCIATORS

ANN-80: Remote LCD Annunciator. Mimics the information
displayed on the FACP’s LCD. Red. (For white, order: ANN-
80-W
.)

ANN-LED: LED Annunciator with three LEDs for each zone:
Alarm, Trouble, and Supervisory. Mounts in the DP-51050(B)
dress panel. (For white, order: ANN-80-W.)

ANN-RLED: LED Annunciator with three alarm (red) indica-
tors for up to 30 input zones or addressable points. (See DF-
60241).

ANN-RLY: Relay module. Mounts inside the cabinet. Provides
ten Form C relays.

ANN-S/PG: Serial/parallel printer gateway. Provides a connec-
tion for a serial or parallel printer.

ANN-I/O: Driver module. Provides connections to a user-sup-
plied graphic annunciator.

ACCESSORIES

DP-51050: Optional dress panel. Restricts access to the sys-
tem wiring while allowing access to the membrane switch
panel.

BB-26: Battery backbox, holds up to two 25 AH batteries and
CHG-75.

BB-55: Battery backbox, holds up to two 25 AH batteries.

TR-CE: Optional trim-ring for semi-flush mounted cabinets.

PRN-6F: UL listed printer.