USER INTERFACE:

Built-in DACT (Digital Alarm Communicator/Transmitter).

Integral 80-character LCD display with backlighting and
keypad.

Real-time clock/calendar with automatic daylight savings
adjustments.

ANN-BUS for connection to remote annunciators.

Audible or silent walk test capabilities.

Piezo sounder for alarm, trouble, and supervisory.

Controls and Indicators

LED INDICATORS

• FIRE ALARM (red)

• SUPERVISORY (yellow)

• TROUBLE (yellow)

• AC POWER (green)

• ALARM SILENCED (yellow)

CONTROL BUTTONS

• ACKNOWLEDGE

• ALARM SILENCE

• SYSTEM RESET (lamp test)

• DRILL

Terminal Blocks

AC Power – TB1:

MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 50/60 HZ,
1.00 A.

MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 50/60 HZ,
3.80 A.

MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ,
2.20 A.

Wire size: minimum 14 AWG (2.00 mm²) with 600 V insulation.
Supervised, nonpower-limited.

Battery (sealed lead acid only) – J12:

Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC
@ 1.4 A. Supervised, nonpower-limited.

Maximum Charger Capacity: 18 AH battery for MS-5UD-3,
and 26 AH battery for MS-10UD-7(E). [Two 18 Ah batteries
can be housed in the FACP cabinet. Larger batteries
require separate battery box such as the BB-26 or BB-55.]

Minimum Battery Size: 7 AH.