Controls and indicators, Terminal blocks – FIREPOWER MS-10UD-7 User Manual
Page 2
Page 2 of 4 — DF-52416:C • 05/12/2009
USER INTERFACE:
•
Built-in DACT (Digital Alarm Communicator/Transmitter).
•
Integral 80-character LCD display with backlighting and
keypad.
•
Real-time clock/calendar with automatic daylight savings
adjustments.
•
ANN-BUS for connection to remote annunciators.
•
Audible or silent walk test capabilities.
•
Piezo sounder for alarm, trouble, and supervisory.
Controls and Indicators
LED INDICATORS
• FIRE ALARM (red)
• SUPERVISORY (yellow)
• TROUBLE (yellow)
• AC POWER (green)
• ALARM SILENCED (yellow)
CONTROL BUTTONS
• ACKNOWLEDGE
• ALARM SILENCE
• SYSTEM RESET (lamp test)
• DRILL
Terminal Blocks
AC Power – TB1:
•
MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 50/60 HZ,
1.00 A.
•
MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 50/60 HZ,
3.80 A.
•
MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ,
2.20 A.
Wire size: minimum 14 AWG (2.00 mm²) with 600 V insulation.
Supervised, nonpower-limited.
Battery (sealed lead acid only) – J12:
•
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC
@ 1.4 A. Supervised, nonpower-limited.
•
Maximum Charger Capacity: 18 AH battery for MS-5UD-3,
and 26 AH battery for MS-10UD-7(E). [Two 18 Ah batteries
can be housed in the FACP cabinet. Larger batteries
require separate battery box such as the BB-26 or BB-55.]
•
Minimum Battery Size: 7 AH.