Dimensions

Width,

mm (in)

Height,

mm (in)

Depth,

mm (in)

Weight,

kg (lb)

System Controller, including base

202 (8.0) 230 (9.1) 81 (3.2) 1.0 (2.2)

Detector, including 'easy fit' base

135 (5.3) 135 (5.3) 135 (5.3) 0.5 (1.1)

Reflector (Single)

100 (3.9) 100 (3.9) 10 (0.4) 0.1 (0.2)

Parameter

Value

Operating Voltage

14—36V DC

Operating Current –

Normal Operation

(including fire or fault activated)

5.5mA - 1 Detector

8mA - 2 Detectors

Operating Current –

Alignment modes - HiA

Alignment modes - LoA

36mA

5.5mA / 8mA

Fire Threshold Range

0.45—3.98 dB

10—60%

Delay to Fire

2—30 s

Delay to Fault

2—30 s

Operating Distance between Detector and Reflector

8—100 m

Maximum angular misalignment of Detector

± 0.3 Deg

Maximum angular misalignment of Reflector

± 5 Deg

Maximum angular movement of Detector head

± 3.5 Deg

Optical wavelength

850 nm

Rapid Obscuration Fault threshold

87%

Operating Temperature (UL Approved)

0—+37.8 Deg C

Operating Temperature (EN54-12 Approved)

-10—+55 Deg C

Operating Temperature (FM Approved)

-20—+55 Deg C

Storage temperature

-40—+85 Deg C

Relative Humidity (non condensing)

93%

IP Rating

IP54

Relay Contact Rating

VFCO, 2A@30VDC

Resistive

Maximum Cable Length (Controller to Detector)

100 m

Cable Gauge

24—14 AWG

0.5—1.6 mm

Housing Flammability rating

UL94 V0

UL File

S3417

CPD Certificate Number

0832-CPD-0565

21. Technical Specifications

Document Number: 0044-033-04-EN