Dimensions
Width,
mm (in)
Height,
mm (in)
Depth,
mm (in)
Weight,
kg (lb)
System Controller, including base
202 (8.0) 230 (9.1) 81 (3.2) 1.0 (2.2)
Detector, including 'easy fit' base
135 (5.3) 135 (5.3) 135 (5.3) 0.5 (1.1)
Reflector (Single)
100 (3.9) 100 (3.9) 10 (0.4) 0.1 (0.2)
Parameter
Value
Operating Voltage
14—36V DC
Operating Current –
Normal Operation
(including fire or fault activated)
5.5mA - 1 Detector
8mA - 2 Detectors
Operating Current –
Alignment modes - HiA
Alignment modes - LoA
36mA
5.5mA / 8mA
Fire Threshold Range
0.45—3.98 dB
10—60%
Delay to Fire
2—30 s
Delay to Fault
2—30 s
Operating Distance between Detector and Reflector
8—100 m
Maximum angular misalignment of Detector
± 0.3 Deg
Maximum angular misalignment of Reflector
± 5 Deg
Maximum angular movement of Detector head
± 3.5 Deg
Optical wavelength
850 nm
Rapid Obscuration Fault threshold
87%
Operating Temperature (UL Approved)
0—+37.8 Deg C
Operating Temperature (EN54-12 Approved)
-10—+55 Deg C
Operating Temperature (FM Approved)
-20—+55 Deg C
Storage temperature
-40—+85 Deg C
Relative Humidity (non condensing)
93%
IP Rating
IP54
Relay Contact Rating
VFCO, 2A@30VDC
Resistive
Maximum Cable Length (Controller to Detector)
100 m
Cable Gauge
24—14 AWG
0.5—1.6 mm
Housing Flammability rating
UL94 V0
UL File
S3417
CPD Certificate Number
0832-CPD-0565
21. Technical Specifications
Document Number: 0044-033-04-EN