Fire Fighting Enterprises FIRERAY 5000 User Manual

Page 10

background image

When ‘Set’ is displayed press

whilst the Reflector is still uncovered

When ‘S-00’ is displayed, cover the Reflector with a non- reflective material and leave

covered, then press

When ‘S-01’ is displayed, uncover the Reflector and leave uncovered, then press

Repeat Steps 8 to 12 for any other Detectors found during the ‘Find’ process

12. ‘Set’ 0/100 (Calibrate)

13. System is Aligned

Green LED on Detector will flash every 10 seconds, and Signal Strength should be between

99% and 101%

Default values: 35% Fire Threshold, 10 second delay to Fire and Fault, Non-Latching mode

10